Digital temperature controller
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Advanced Function Setting Level
lbab
LBA Band
Function
Setting
See
See
out1
Control Output 1 Assignment
Function
Setting
See
See
• This parameter sets the LBA band.
• If a control deviation greater than the LBA band is not reduced when the
LBA level is exceeded, an loop burnout is detected.
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
Controllers with Analog Inputs
Note
Set "none" as the unit for Controllers with Analog Inputs.
■ Related Parameters
Process value/set point (operation level): Page 120
Alarm 1 type (initial setting level): Page 152
LBA detection time, LBA level (advanced function setting level): Page 176
• This parameter sets the function to be assigned to control output 1.
None: No function is assigned to control output 1.
o:
Heating control output is output.
c-o:
Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output. (See note 2.)
alm2: Alarm 2 is output. (See note 2.)
alm3: Alarm 3 is output. (See note 2.)
p.end: Program end is output. (See notes 2 and 3.)
(1) If c-o is assigned for standard control, a value equivalent to 0% is output.
Note
(2) Can be selected for relay and voltage outputs only.
(3) Can be selected only when the program pattern is not set to OFF.
■ Related Parameters
Standard or heating/cooling: Page 150, Program pattern: Page 151, Transfer
output type: Page 155 (initial setting level)
Models
0.0 to 999.9
0.00 to 99.99
Setting range
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
The LBA detection time must not be
0.
Setting range
Unit
C or F
(See note.)
%FS
The transfer output type must be set
to OFF when the control output is a
current output.
Section 5-7
Default
3.0
0.20
Default
o
177