Table 18.
Sizing natural gas pipe mains and branches
Gas Input (Cubic Feet/Hour)*
Gas Supply
Pipe Run
1-¼"
1-½"
(ft)
Pipe
Pipe
10
1050
1600
20
730
1100
30
590
890
40
500
760
50
440
670
60
400
610
70
370
560
80
350
530
90
320
490
100
305
460
125
275
410
150
250
380
175
225
350
200
210
320
* Table is based on a specific gravity of 0.60. Use
gravity of the local gas supply.
Table 19.
Modulating gas heat settings
Heater Size (MBH)
Gas Orifice
500
850
1000
Heater Size (MBH)
Gas Orifice
500
850
1000
Note: Valve actuator settings are approximate and may require "fine tuning" to properly set. Right (fine) settings given are in notches from the "zero"
midpoint location on sight gage.
RT-SVX36K-EN
2"
2-½"
3"
Pipe
Pipe
Pipe
3050
4800
8500
2100
3300
5900
1650
2700
4700
1450
2300
4100
1270
2000
3600
1150
1850
3250
1050
1700
3000
990
1600
2800
930
1500
2600
870
1400
2500
780
1250
2200
710
1130
2000
650
1050
1850
610
980
1700
Table 23
for the specific
Full Modulation
Air Damper
Actuator Voltage
Range (VDC)
#21
7 - 10
#H
6 - 10
#N
5 - 10
Full Modulation
Air Damper
Actuator Voltage
Range (VDC)
#34 / #53
7 - 10
#32
6 - 10
#29
5 - 10
4"
Pipe
17500
12000
9700
8300
7400
6800
6200
5800
5400
5100
4500
4100
3800
3500
Natural Gas
Partial Modulation
Air Damper
Actuator Voltage
Range (VDC)
7 - 9.7
6 - 8.7
5 - 8.7
LP
Partial Modulation
Air Damper
Actuator Voltage
Range (VDC)
7 - 9.7
6 - 8.7
5 - 8.7
Installation
Gas Valve Settings
Left Setting
Right Setting
Pgas/ Pair
(Low fire bias)
2.3
-1
1.3
-1
0.9
0
Gas Valve Settings
Left Setting
Right Setting
Pgas/ Pair
(Low fire bias)
6
1
3.2
1
1.9
0
49