24-89 Ton - Evaporative Condenser - Trane IntelliPak Installation, Operation And Maintenance Manual

Intellipak series commercial rooftop air conditioners with cv, vav, or szvav controls
Hide thumbs Also See for IntelliPak:
Table of Contents

Advertisement

Table 63. Critical control parameters
Notes:
1. Using the Human Interface (HI), go to SETUP Menu and input setting for parameters listed below.
2. Use the map shown below to determine region of country based on unit site location.
3. Fixed Speed compressor units 8F deadband
4. eFlex compressor units 4F deadband
Supply Air Temperature Control Setpoint
Supply Air Temperature Deadband
Supply Air Pressure Setpoint
Supply Air Pressure Deadband
Building Static Pressure Setpoint
Building Static Pressure Deadband
Standby Freeze Avoidance
Exhaust Enable Setpoint
Economizer Minimum Position Setpoint
Fixed Dry Bulb Economizer C/O
Type a (Moist)*
Fixed Dry Bulb Economizer C/O
Type b (Dry)*
Fixed Dry Bulb Economizer C/O
Type c (Marine)*
Fixed Reference
Enthalpy Changeover
Differential Comparative
Enthalpy Changeover
Note: See map
(Figure 124, p.
Examples:
(a) Minneapolis, Minnesota is in "Region 6" and resides in "Moist" subregion, thus designation is 6b. Economizer changeover setting
should be 75°F.
(b) Charleston, South Carolina is in "Region 3" and resides in "Moist" subregion, thus the designation is 3c. Economizer changeover setting
should be 65°F.
24-89 Ton — Evaporative Condenser
Important: Water treatment is required before
beginning startup. Failure to do so will
damage the unit and result in premature
unit degradation.
This checklist is intended to be a guide for the start up
technician. Many of the recommended checks and actions
Job Name
Job Location
Sales Order #
Unit DL # (special units)
Starting Sales Office
RT-SVX36K-EN
Suggested
Parameter
55°F
8°F
1.8" w.c.
0.1" w.c.
0.03" w.c.
0.04" w.c.
20%
10%
10%
T
> 75°F
OA
H
> 28 Btu
OA
H
> H
OA
RA
164) below for dry bulb changeover.
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
T
> 65°F T
> 65°F T
> 65°F T
OA
OA
OA
T
> 75°F T
OA
could expose the technician to electrical and mechanical
hazards. Refer to the appropriate sections in the unit IOM
for appropriate procedures, component specifications and
safety instructions.
Important: This checklist is not intended to be a
substitution for the contractors installation
instruction.
Serial #
Model #
Ship Date
Date
Technician
Startup Checklists
> 65°F T
> 70°F T
> 70°F T
OA
OA
OA
> 75°F T
> 75°F
OA
OA
> 70°F
OA
157