Unit Start Up
Figure 72. Supply fan performance with or without variable frequency drive - 60, 70 and 75 ton air-cooled, 73, 80 and
89 ton evaporative condensing - forward curved
8.0
1200 RPM
7.5
1100 RPM
7.0
6.5
1000 RPM
6.0
5.5
5.0
900 RPM
4.5
4.0
800 RPM
3.5
3.0
700 RPM
2.5
600 RPM
2.0
1.5
500 RPM
1.0
0.5
0.0
0
3000
6000
Figure 73. Supply fan performance with variable frequency drive - 60 ton air-cooled, 73 ton evaporative condensing -
direct drive plenum, 80% width
8.0
7.5
2000 RPM
7.0
1900 RPM
6.5
6.0
1800 RPM
5.5
1700 RPM
5.0
1600 RPM
4.5
1500 RPM
4.0
1400 RPM
3.5
1300 RPM
3.0
1200 RPM
2.5
1100 RPM
2.0
1000 RPM
1.5
1.0
0.5
0.0
0
2500
5000
112
9000
12000
15000
Airflow, CFM
2100 RPM
2200 RPM
7500
10000
12500
15000
Airflow, CFM
18000
21000
24000
17500
20000
22500
25000
S_HL*60, *70, *75 Ton
*73, *80, *89 Ton
Dual 22 X 22 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 50
- Maximum Fan RPM = 1130
- Maximum CFM = 27,000
- Maximum Static Pressure
Leaving the unit = 4.0" w.c.
70%
80%
90%
27000
30000
S_HL*60/73 Ton
Dual 25" 80% Width DDP Fan
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Total Motor HP = 10 (2x5HP)
- Maximum Total Motor HP = 40 (2x20HP)
- Maximum Fan RPM = 2200
- Maximum CFM = 27,000
- Maximum Static Pressure Leaving the
unit = 4.0" w.c.
27500