Trane IntelliPak Installation, Operation And Maintenance Manual page 108

Intellipak series commercial rooftop air conditioners with cv, vav, or szvav controls
Hide thumbs Also See for IntelliPak:
Table of Contents

Advertisement

Unit Start Up
Figure 64. Supply fan performance with variable frequency drive — 30 ton air-cooled, 36 ton evaporative condensing -
direct drive plenum, 80% width
8.0
7.5
2000 RPM
7.0
1900 RPM
6.5
6.0
1800 RPM
5.5
1700 RPM
5.0
1600 RPM
4.5
1500 RPM
4.0
1400 RPM
3.5
1300 RPM
3.0
1200 RPM
2.5
1100 RPM
2.0
1000 RPM
1.5
1.0
0.5
0.0
0
1000
2000
3000
Figure 65. Supply fan performance with variable frequency drive — 30 ton air-cooled, 36 ton evaporative condensing -
direct drive plenum, 120% width
8.0
7.5
7.0
6.5
6.0
1800 RPM
5.5
1700 RPM
5.0
1600 RPM
4.5
1500 RPM
4.0
1400 RPM
3.5
1300 RPM
3.0
1200 RPM
2.5
1100 RPM
2.0
1000 RPM
1.5
1.0
0.5
0.0
0
1000
2000
3000
108
4000
5000
6000
7000
8000
Airflow, CFM
2100 RPM
2000 RPM
1900 RPM
4000
5000
6000
7000
8000
Airflow, CFM
9000
10000
11000
12000
13000
9000
10000
11000
12000
13000
S_HL*30/36 Ton
Single 25" 80% Width
DDP Fan
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 3
- Maximum Motor HP = 20
- Maximum Fan RPM = 2200
- Maximum CFM = 13,500
- Maximum Static Pressure
Leaving the unit = 4.0" w.c.
14000
15000
S_HL*30/36 Ton
Single 25" 120% Width
DDP Fan
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 3
- Maximum Motor HP = 20
- Maximum Fan RPM = 2100
- Maximum CFM = 13,500
- Maximum Static Pressure
Leaving the unit = 4.0" w.c.
14000
15000
RT-SVX36K-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents