Startup Checklists
Table 65. Critical control parameters
Notes:
1. Using the Human Interface (HI), go to SETUP Menu and input setting for parameters listed below.
2. Use the map shown below to determine region of country based on unit site location.
3. Fixed Speed compressor units 8F deadband
Supply Air Temperature Control Setpoint
Supply Air Temperature Deadband
Supply Air Pressure Setpoint
Supply Air Pressure Deadband
Building Static Pressure Setpoint
Building Static Pressure Deadband
Standby Freeze Avoidance
Exhaust Enable Setpoint
Economizer Minimum Position Setpoint
Fixed Dry Bulb Economizer C/O
Type a (Moist)*
Fixed Dry Bulb Economizer C/O
Type b (Dry)*
Fixed Dry Bulb Economizer C/O
Type c (Marine)*
Fixed Reference
Enthalpy Changeover
Differential Comparative
Enthalpy Changeover
Note: See map
(Figure 124, p.
Examples:
(a) Minneapolis, Minnesota is in "Region 6" and resides in "Moist" subregion, thus designation is 6b. Economizer changeover setting
should be 75°F.
(b) Charleston, South Carolina is in "Region 3" and resides in "Moist" subregion, thus the designation is 3c. Economizer changeover setting
should be 65°F.
160
Suggested
Parameter
55°F
8°F
1.8" w.c.
0.1" w.c.
0.03" w.c.
0.04" w.c.
20%
10%
10%
T
> 75°F
OA
H
> 28 Btu
OA
H
> H
OA
RA
164) below for dry bulb changeover.
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
T
> 65°F T
> 65°F T
> 65°F T
OA
OA
OA
T
> 75°F T
OA
> 65°F T
> 70°F T
> 70°F T
OA
OA
OA
> 75°F T
> 75°F
OA
OA
RT-SVX36K-EN
> 70°F