Unit Start Up
Figure 68. Supply fan performance with variable frequency drive - 40 ton air-cooled, 48 ton evaporative condensing -
direct drive plenum, 120% width
8.0
7.5
7.0
6.5
1700 RPM
6.0
1600 RPM
5.5
5.0
1500 RPM
4.5
1400 RPM
4.0
1300 RPM
3.5
1200 RPM
3.0
1100 RPM
2.5
1000 RPM
2.0
1.5
1.0
0.5
0.0
0
2000
4000
\
Figure 69. Supply fan performance with variable frequency drive - 50, 55 ton air-cooled, 59 ton evaporative condensing -
direct drive plenum, 80% width
8.0
1700 RPM
7.5
1600 RPM
7.0
6.5
1500 RPM
6.0
5.5
1400 RPM
5.0
1300 RPM
4.5
4.0
1200 RPM
3.5
1100 RPM
3.0
1000 RPM
2.5
2.0
1.5
1.0
0.5
0.0
0
2500
5000
110
1900 RPM
1800 RPM
6000
8000
10000
Airflow, CFM
1800 RPM
7500
10000
12500
Airflow, CFM
12000
14000
16000
15000
17500
20000
22500
S_HL*40/48 Ton
Single 27" 120% Width
DDP Fan
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 3
- Maximum Motor HP = 25
- Maximum Fan RPM = 1900
- Maximum CFM = 18,000
- Maximum Static Pressure
Leaving the unit = 4.0" w.c.
18000
20000
S_HL*50/59 & 55 Ton
Single 30" 80% Width
DDP Fan
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 30
- Maximum Motor HP = 30
- Maximum Fan RPM = 1800
- Maximum CFM = 22,500
- Maximum Static Pressure
Leaving the unit = 4.0" w.c.