Trane IntelliPak Installation, Operation And Maintenance Manual page 176

Intellipak series commercial rooftop air conditioners with cv, vav, or szvav controls
Hide thumbs Also See for IntelliPak:
Table of Contents

Advertisement

Maintenance
Table 78. Supply and exhaust/return fan VFD programming parameters (continued)
Menu
1-20 (TR150)
1-21 (TR200)
Load and Motor
Brakes
Reference / Ramps
Limits / Warnings
Digital In/Out
Analog In/Out
176
ID
Name
1-03
Torque Characteristics
Motor Power [HP]
1-22
Motor Voltage
1-23
Motor Frequency
1-24
Motor Current
1-25
Motor Nominal Speed
1-39
Motor Poles
1-73
Flying Start
1-90
Motor Thermal Protection
2-00
DC Hold/Preheat Current
2-01
DC Brake Current
DC Brake Cut In Speed
2-04
[Hz]
3-03
Maximum Reference
3-16
Reference 2 Source
3-17
Reference 3 Source
3-41
Ramp 1 Ramp up Time
3-42
Ramp 1 Ramp Down Time
Motor Speed Low Limit
4-12
[Hz]
Motor Speed High Limit
4-14
[Hz]
4-18
Current Limit
4-19
Max Output Frequency
5-12
Terminal 27 Digital Input
5-13
Terminal 29 Digital Input
5-40
Function Relay
Terminal 53 Low Ref./
6-14
Feedb. Value
Terminal 53 High Ref./
6-15
Feedb. Value
FC
Variable Torque
Per Motor Nameplate HP
Nameplate HP [dual motors
Per Motor Nameplate
Voltage
Per Motor Nameplate
Per Motor Nameplate FLA
Nameplate FLA [dual motors
Per Motor Nameplate Rated
Per Motor Nameplate Rated
Speed
6 if Motor Nameplate Rated
4
4 if Motor Nameplate Rated
Enabled
ETR Trip1
0
0
10
60
No function
No function
30
30
22
81.8 - 20, 24, 25, 29T Units
67.8 - 30, 36, 40, 48, 70, 75,
61.7 - 50, 55, 59T Units
60
120 - 20, 24, 25, 29T Units
101.7 - 30, 36, 40, 48, 70,
92.5 - 50, 55, 59T Units
100
60
Coast inverse
No operation
Relay 1 active No alarm,
Relay 1 active No alarm,
Relay 2 active Motor
Running
(Relay 1 [160], Relay 2 [5])
(Relay 1 [160], Relay 2 [5])
22
60
DDP
Variable Torque
Sum of HP Per Motor
on 60-75T]
Per Motor Nameplate
Voltage
Per Motor Nameplate
Sum of FLA Per Motor
on 60-75T]
Speed
Speed ~1200 RPM
Speed > 1200 RPM
Enabled
ETR Trip1
0
0
10
83 (4-pole motor), 120
(6-pole motor)
No function
No function
30
30
15
If ID139 = 4 poles then
75.6 - 60, 73T Units
80, 89T Units
If ID139 = 6 poles then
113.4 - 60, 73T Units
75, 80, 89T Units
100
120
Coast inverse
No operation
Relay 2 active Motor
Running
15
83 (4-pole motor), 120
(6-pole motor)
RT-SVX36K-EN
Unit
hp
V
Hz
A
RPM
%
%
Hz
Hz
s
s
Hz
Hz
%
Hz