Trane IntelliPak Installation, Operation And Maintenance Manual page 123

Intellipak series commercial rooftop air conditioners with cv, vav, or szvav controls
Hide thumbs Also See for IntelliPak:
Table of Contents

Advertisement

Table 53. 90-130 Tons - 50% exhaust fan performance
Nominal CFM
Tons
Std
0.250
(AC/EC)
Air
RPM BHP RPM
12000 432 4.09
14000 495 6.40
90-130
16000 559 9.46
18000 623 13.36 643
20000 688 18.23 707
Note: Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
Table 54. Return fan performance—20, 25, 30 tons AC; 24, 29, 36 tons EC (24.5")
CFM
Std.
0.25
Air
RPM
BHP
RPM
4000
557
0.29
638
4500
605
0.36
682
5000
654
0.44
727
5500
704
0.53
773
6000
756
0.64
821
6500
808
0.76
868
7000
861
0.90
917
7500
913
1.06
968
8000
967
1.24
1019
8500
1021
1.44
1071
9000
1075
1.67
1123
9500
1130
1.92
1175
10000
1186
2.20
1228
10500
1241
2.50
1280
11000
1297
2.84
1334
11500
1353
3.20
1387
12000
1408
3.60
1441
12500
1464
4.03
1496
13000
1520
4.49
1551
13500
1576
4.99
1606
14000
1633
5.52
1661
Notes:
1. Max fan RPM 1715 for 24.5" Class I Fan
2. Max motors Available are as follows: 20T: 3HP, 25T: 5HP, 30T: 7.5 HP
3. Max CFM available is as follows; 20T: 9000, 25T: 11000, & 30T: 13500
4. Min CFM is 4000 for 20T, 25T, & 30T
5. Return fan belt drive RPM selections will be available to cover 500-1600 RPM range +/- 50 RPM
6. Performance data includes cabinet and rain hood effect. Damper pressure drop must be added to the return duct static per
7. Shaded area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.
RT-SVX36K-EN
Negative Static Pressure (In. W.G.)
0.500
0.750
1.000
BHP
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
461
4.31
502 4.86
545 5.67
519
6.65
547 6.96
582 7.64
581
9.77
602 10.02 628 10.45 658 11.20 690 12.19 723 13.32 753 14.22 784 15.18 811 16.27
13.73
662 14.05 680 14.31 705 14.83 732 15.63 759 16.65 788 17.88 817 19.13 844 20.12
18.66
724 19.03 741 19.36 757 19.65 779 20.22 804 21.04 827 22.07 853 23.31 879 24.70
Negative Static Pressure
0.50
0.75
BHP
RPM
BHP
RPM
0.48
710
0.68
776
0.57
749
0.79
811
0.67
790
0.91
850
0.79
834
1.04
889
0.92
879
1.20
932
1.06
925
1.36
976
1.21
972
1.55
1021
1.39
1019
1.74
1068
1.58
1068
1.96
1115
1.80
1116
2.19
1162
2.04
1166
2.45
1210
2.31
1217
2.73
1258
2.60
1269
3.04
1307
2.92
1321
3.37
1357
3.27
1373
3.74
1409
3.64
1425
4.13
1460
4.06
1477
4.56
1512
4.50
1530
5.01
1565
4.98
1583
5.51
1617
5.50
1636
6.03
1669
6.05
1690
6.60
1721
1.250
1.500
585
6.35 622 7.19 655 7.99 686
619
8.57 655 9.42 689 10.26 721 11.26 750 12.21 777 13.14
1.00
1.25
BHP
RPM
BHP
RPM
0.89
838
1.10
899
1.02
869
1.25
926
1.16
905
1.41
957
1.30
943
1.58
992
1.47
982
1.77
1030
1.66
1024
1.97
1070
1.87
1067
2.19
1112
2.10
1112
2.44
1155
2.34
1158
2.71
1199
2.60
1204
3.00
1244
2.88
1252
3.30
1290
3.17
1299
3.62
1337
3.50
1347
3.97
1384
3.85
1395
4.34
1432
4.23
1443
4.74
1480
4.64
1493
5.16
1528
5.08
1544
5.62
1576
5.56
1596
6.11
1626
6.06
1648
6.64
1677
6.60
1700
7.20
1728
7.19
1752
7.79
1780
Unit Start Up
1.750
2.000
2.250
8.78 717 9.57
1.50
1.75
BHP
RPM
BHP
RPM
1.32
969
1.60
1038
1.49
980
1.73
1033
1.67
1007
1.93
1057
1.86
1040
2.15
1087
2.06
1076
2.38
1121
2.29
1114
2.61
1157
2.53
1154
2.87
1195
2.79
1196
3.15
1235
3.08
1238
3.45
1277
3.39
1283
3.79
1320
3.72
1327
4.14
1363
4.07
1373
4.52
1408
4.45
1419
4.91
1454
4.85
1466
5.33
1500
5.26
1515
5.79
1546
5.71
1561
6.25
1594
6.18
1610
6.75
1642
6.68
1658
7.28
1689
7.22
1707
7.84
1737
7.80
1756
8.42
1785
8.42
1807
9.05
1834
Table 49, p. 120
2.500
748 10.48
2.00
BHP
1.89
1.99
2.20
2.44
2.70
2.95
3.22
3.51
3.84
4.19
4.56
4.96
5.38
5.84
6.29
6.79
7.32
7.87
8.44
9.06
9.70
123