Changing Between Float Charge and Equalize Charge

The procedure to change the recharge mode between float charge and equalize charge is shown in Steps
1-3.
See the Note below for an explanation of Float and Equalize charge modes.
LED Key
- LED Off
- LED On
- LED Flash
UPS SUPPLY
AC - Vo 480 V
AC - Io 50%
AC INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
UPS SUPPLY
AC - Vo 480 V
AC - Io 50%
AC INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
68
UPS
INVERTER
AC
SWITCH
AC OUTPUT
BYPASS
UPS
INVERTER
AC
SWITCH
AC OUTPUT
BYPASS
STEP 1
Make sure that the FLOAT CHARGE LED is
"ON".
STEP 2
Press FLOAT/EQUAL button for at least 0.5
sec.
Change completed.
EQUAL CHARGE LED is "ON".
FLOAT CHARGE LED is "OFF"
STEP 3
Please wait until procedure is completed.
NOTE
In equalize charge mode, the battery is
charged for a programmed period at a
specified voltage (depending on the battery
spec), rather than the float charge, in order
to prevent voltage deviations among battery
cells. This should be done once every six
months if possible.
The G8000 UPS will automatically perform
the equalize recharge after battery backup
operation.
G8000 Series Installation and Operation Manual