Fault Messages - Toshiba G8000 SERIES Installation And Operation Manual

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

15.4

Fault Messages

Figure 15.4 show the locations for fault detection. Tables 15.3 through 15.7 gives details for the fault and
warning messages referred to in section "Fault Data Screen." The "item" code associated with each fault
or warning message may be used to determine the physical location of the fault or warning by referring to
Figure 15.4. The UPS unit may be shipped with different protective configurations from the standard shown
in Figure 15.4, if specified by the customer. See the protective configuration indicated on the single line
diagram for each UPS.
47S
95S
27S
59S
52R
5E
80PS
80B1
30ST
48
ITEM
LCD MESSAGE INDICATION
26
OVER HEAT
30ST
(NO INDICATION)
48
STARTUP ERR
5E
EMG.STOP
71F
FUSE BLOWN
76
DC OC
80B2
BATT. UV
80PS
CONT. PS. ERR
TABLE 15.4 - WARNING – 1 (CONVERTER STOP/INPUT POWER ERROR)
ITEM
LCD MESSAGE INDICATION
27S
AC I/P UV
47S
AC PHASE ERR
59S
AC I/P OV
95S
I/P FREQ. ERR
G8000 Series Installation and Operation Manual
45
Inverter
Battery
Chopper
76C
76
80B2
26B
95C
59C
47C
27C
FIGURE 15.4 - PROTECTIVE DETECTOR LOCATIONS
TABLE 15.3 - FAULT (TRIP)
HIGH TEMP IN THE CABINET.
AN ERROR OCCURRED IN THE MAIN CONTROL MICROPROCESSOR (CPU).
STARTUP WAS NOT COMPLETED WITHIN THE NORMAL TIME FRAME.
AN EMERGENCY STOP WAS ACTIVATED VIA THE EXTERNAL CONTACT.
RECTIFIER, DC, OR INVERTER MAIN CIRCUIT FUSE BLOWN.
DC OVER-CURRENT - EXCESSIVE CURRENT IN DC CIRCUIT.
BATTERY VOLTAGE IS BELOW CUTOFF VOLTAGE.
THE CONTROL POWER SUPPLY VOLTAGE FAILED.
AC INPUT UNDERVOLTAGE - AC INPUT VOLTAGE IS TOO LOW.
AC INPUT PHASE ROTATION ERROR.
AC INPUT OVERVOLTAGE - AC INPUT VOLTAGE IS TOO HIGH.
AC INPUT FREQUENCY ERROR.
51I
30U
26
71F
DESCRIPTION
DESCRIPTION
59I
49
271
83MC1
83MC
83BF
73