5. On Output cabinet: Open the door. Insert Neutral bus between the cabinets as
shown in FIG. 5 & FIG. 6 and connect on corresponding output and input cabinet
neutral bus using 3/8-16X1.25" bolt, flat, belleville washer and nut (supplied).
Insert Belleville washer between flat washer and nut.
6. Insert AC Bus (qty. 3) between the cabinets as shown in FIG. 5 & FIG. 6 and connect
on corresponding output and input cabinet AC bus using 1/2-13X1.25" bolt, flat, bel-
leville washer and nut (supplied).
Insert Belleville washer between flat washer and nut.
7. Insert DC Bus (qty. 2) between the cabinets as shown in FIG. 5 & FIG. 6 and con-
nect on corresponding output and input cabinet DC bus using 1/2-13X1.25" bolt, flat,
belleville washer and nut (supplied).