MEASUREMENT SCREENS
O/P CURRENT (PEAK)
U
50[%]
V
50[%]
W
50[%]
AC INPUT
AC I/P-V 480[V]
FREQ. 60.0[Hz]
BYPASS INPUT
BYP I/P-V 480[V]
FREQ.
60.0[Hz]
DC INPUT
DC-V
632[V]
BATT-V 400[V]
BATT- I
0[A]
MODE COUNT
UPS
35[H]
BATTERY
56[MIN]
32[TIM]
CLOCK
TIME 03-24-06 13:58
58
TABLE 13.3 - CONTINUED
Shows the peak output current peak (%) for each phase.
Peak value of output current
RMS value for rated current x 1.41
Shows the AC Input Voltage (line-to-line) and frequency.
Shows the Bypass Input Voltage (line-to-line voltage) and
frequency.
Shows the internal DC bus voltage, battery voltage and
battery current.
The battery current value displayed is negative during
recharge and positive during discharge.
Shows the cumulative UPS operation time, the
cumulative battery backup time and the number of battery
backup operations.
The current time is displayed if there are no faults
recorded, or after the reset button is pressed.
Date is displayed in the mm-ddyyy format. The unit does
not calculate daylight savings time.
Time is displayed in the 24-hour format (e.g. 1:58 P.M. =
1358 Hrs.)
G8000 Series Installation and Operation Manual
x 100 [%]