225Kva Ipg - Toshiba G8000 SERIES Installation And Operation Manual

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

225kVA IPG

TOSHIBA
Installation Planning Guide for 225kVA UPS
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K22KK6XSxx)
Dimensions
(W x D x H)
Inches
55.1" x 31.8" x. 79.2"
Maximum Input Power Demand
Normal Mode (Recharge Mode)
kVA
PF
247 (258)
>0.99
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)
Maximum Input Power
Demand
kVA
PF
Amps
225
1.0
271
DC Backup Input (Battery - 360VDC Nom./Flywheel 550VDC Nom.)
DC Capacity for Full
Backup System
Load Output
kWB
Battery
242
* If required. Most Battery and Flywheel Cabinets are equipped with built-in breakers.
Rated Output Power
kVA
PF
Amps
225
1.0
271
Important Notes:
1. CABLE ACCESS – Top and Bottom.
2. Maximum Current required at Primary AC Input based on full
load output and maximum battery charging current.
3. Output load conductors are to be installed in separate
conduit from input conductors.
4. Control wires and power wires are to be installed in separate
conduits.
5. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
6. Wiring shall comply with all applicable national and local
electrical codes.
7. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
- Alternate AC Input: 3φ, 4-wire + ground.
- AC Output: 3φ, 4-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
8. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
9. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
10. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
11. Weights do not include batteries or other auxiliary equipment
external to the UPS.
Rev. 2.3
G8000 Series Installation and Operation Manual
G8000 Series UPS
General Mechanical Information
Floor
Approximate Full-Load
Weight
Loading
Heat Rejection
2
Lbs.
Lbs./ft.
Btu/Hr
2,980
245
67,667
Primary AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
Amps
297 (311)
400 AT
Suggested External
Overcurrent Protection
Amps
350 AT
(2) x 4/0 – (2) x 250 kcmil // (4) x 4/0 – (4) x 250 kcmil
Maximum Discharge
Suggested External
at Full Load Output
Overcurrent Protection*
Amps DC
805
AC Output (480/277V 3-Phase / 4-Wire)
Suggested External
Overcurrent Protection
Amps
350 AT
(2) x 4/0 – (2) x 250 kcmil // (4) x 4/0 – (4) x 250 kcmil
12. Cable sizing calculations based on the following assumptions:
13. Ratings of wires and overcurrent devices are suggested
TOSHIBA
13131 West Little York Road
Houston, TX 77041
Telephone: (877) 867-8773
Fax: (713) 896-5212
Web Site:
Page 1 of 3
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Top
Front
Bottom
15.75"
43.5"
0"
External Feeder Wire Size: Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
(2) x 3/0 – (2) x 4/0
External Feeder Wire Size:
Min. – Max. Per Phase // Min. – Max. for Neutral
AWG or kcmil at 75º C Temp. Rating
External Feeder Wire Size:
Min. – Max.
Amps
AWG or kcmil at 75º C Temp. Rating
900 A
(4) x 4/0 – (4) x 250 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase // Min. – Max. for Neutral
AWG or kcmil at 75º C Temp. Rating
- Minimum size is smallest size based on ampacity at 30 °C.
- Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
- Neutral sized for 2X phase current.
- Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
- Temperature rating of copper conductors/terminals: 75 °C.
- Reference: 2005 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
INTERNATIONAL CORPORATION
www.toshiba.com/ind
G8000-IPG-225kVA
Sides
Back
0"
0"
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents