11.6

Control Wires

The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.8.
No.
I/O
1
Output
2
Output
3
Output
4
Output
5
Output
6
Input
7
Input
8
Input
9
Input
10
Output
11
Output
12
Input
13
Input
14
Output
15
Output
16
Output
17
Output
18
Output
19
Output
20
21
Output
22
Output
Note: All control wiring should be #18 AWG (0.823 mm
44
TABLE 11.8 EXTERNAL CONNECTIONS
Signal Name
Low Battery
Backup Operation
Fault
Inverter Supply
Warning
}
P24
Remote Run
}
P24
Remote Stop
Bypass Supply
Output Signal Ground
}
P24
Battery Overheat
}
52C Trip Signal
}
72B Trip Signal
}
72B Aux. Contact
}
External EPO
External EPO
Operation
Closed at Low Battery
Closed during Backup Operation
Closed if Faults present
Closed during Normal Operation
Closed if Warnings present
Close to run UPS
Close to stop UPS
Close during Bypass Operation
(Ground for pin #1 – 5 & #10)
Battery's
Overheat B-contact
Bypass Breaker
Shunt Trip Signal by EPO
Battery Breaker shunt trip
by EPO or Battery shutdown
Battery breaker's
Auxiliary A-contact
Ext EPO (Customer) N.O. Contacts
Ext EPO (Customer) N.O. Contacts
) or larger.
2