Toshiba G8000 SERIES Installation And Operation Manual page 51

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

Figure 11.12 shows the four (4) cable landing plates provided at the top of the 300 kVA UPS. Seven (7)
holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the
conduit landing plates.
3.93 in.
3.15 in.
21.26 in.
37.4 in.
GROUND
CONTROL
WIRE
WIRES
AC
AC OUT-
BATTERY
BATTERY
BYPASS
INPUT
PUT
0.76 in.
Recommended
56.70 in.
Conduit Placement
Order in Top Conduit
CONDUIT LANDING PLATES - DIMENSIONS
Landing Plates
FIGURE 11.12 - TOP ACCESS CONDUIT LANDING PLATES (300 KVA)
Figure 11.13 shows the three (3) conduit landing plates provided at the top of the 500 kVA UPS. The
dashed rectangle indicates the UPS opening behind the conduit landing plates.
Ensure that your installation adheres to local and NEC electrical codes.
CABLE ENTRY PLATE
CABLE ENTRY PLATE
CABLE ENTRY PLATE
(AC INPUT, BYPASS INPUT)
AC OUTPUT, DC INPUT
(CONTROL)
28.0" X 6.3" (711 MM X 161 MM)
28.0" X 6.3" (711 MM X 161 MM)
28.0" X 6.3" (711 MM X 161 MM)
FIGURE 11.13 - TOP CONDUIT LANDING PLATES FOR THE 500 KVA UPS
41
G8000 Series Installation and Operation Manual