Toshiba G8000 SERIES Installation And Operation Manual page 46

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

See Table 11.5 – Table 11.6 for recommended cable sizes for the 150, 225, 300 and 500 kVA UPS.
TABLE 11.3 RECOMMENDED CRIMP TYPE COMPRESSION LUGS FOR BUS STRIP TERMINALS
Wire Size
1/0
B
I
B
2/0
B
I
B
3/0
B
I
B
4/0
B
I
B
300 MCM
B
I
B
350 MCM
B
I
600 MCM
B
I
TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT
Recommended external cable sizes for both 75 °C and 90 °C copper wire for minimum battery configurations
are listed in Table 11.4–11.7. For extended runtime battery strings configurations consult with Toshiba
Technical Support. Ensure that your installation adheres to local and NEC electrical codes.
36
Wire
Recommendation
Strand
Class
Vendor
Cat. No.
Burndy
YA25
Ilsco
CRA-1/OL
Burndy
YA25-LB
Burndy
YA26
Ilsco
CRA-2/OL
Burndy
YA27-LB
Burndy
YA-27
Ilsco
CRB-3/OL
Burndy
YA28-LB
Burndy
YA28
Ilsco
CRB-4/OL
Burndy
YA29-LB
Burndy
YA30
Ilsco
CRA-30OL
Burndy
YA32-LB
Burndy
YA31L
Ilsco
CRA-350
Burndy
YA36L
Ilsco
CRA-600
(USE 75 °C Copper Wire)
Crimp tool Required
Burndy type Y35 or Y46
Color Key
Die Index
Pink
12 / 348
Pink
12 / 348
Black
13
Black
13
Black
13
Orange
14 / 101
Orange
14 / 101
Orange
14 / 101
Purple
15
Purple
15
Purple
15
Yellow
16
White
17 / 298
White
17 / 298
Red
18 / 324
Red
18
Red
18
Green
22
Green
22
G8000 Series Installation and Operation Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents