Input Power Supply Circuit; Connection Example - Mitsubishi Electric Melservo-J2-SUPER series Instruction Manual

General-purpose ac servo
Hide thumbs Also See for Melservo-J2-SUPER series:
Table of Contents

Advertisement

3. SIGNALS AND WIRING

3.7 Input power supply circuit

CAUTION

3.7.1 Connection example

Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as
alarm occurrence is detected and power is shut off.
A no-fuse breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230VAC power supply
3-phase
200 to 230 VAC
When the servo amplifier has become faulty, switch power off on the servo
amplifier power side. Continuous flow of a large current may cause a fire.
Use the trouble signal to switch power off. Otherwise, a regenerative brake
transistor fault or the like may overheat the regenerative brake resistor, causing a
fire.
Forced
stop
RA
NFB
MC
Forced stop
Servo-on
ON
OFF
MC
Servo amplifier
L
1
L
2
L
3
L
11
L
21
EMG
SON
SG
VDD
COM
ALM
3 - 23
MC
SK
RA
Trouble

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents