Power Supply Equipment Capacity And Generated Loss - Mitsubishi Electric Melservo-J2-SUPER series Instruction Manual

General-purpose ac servo
Hide thumbs Also See for Melservo-J2-SUPER series:
Table of Contents

Advertisement

13. CHARACTERISTICS

13.2 Power supply equipment capacity and generated loss

(1) Amount of heat generated by the servo amplifier
Table 12.1 indicates servo amplifiers' power supply capacities and losses generated under rated load.
For thermal design of an enclosure, use the values in Table 13.1 in consideration for the worst
operating conditions. The actual amount of generated heat will be intermediate between values at
rated torque and servo-off according to the duty used during operation. When the servo motor is run at
less than the maximum speed, the power supply capacity will be smaller than the value in the table,
but the servo amplifier's generated heat will not change.
Table 13.1 Power supply capacity and generated heat per servo amplifier at rated output
Servo amplifier
Servo motor
HC-KFS053 13
HC-MFS053 13
MR-J2S-10CL (1)
HC-UFS13
HC-KFS23
MR-J2S-20CL (1)
HC-MFS23
HC-UFS23
HC-KFS43
MR-J2S-40CL (1)
HC-MFS43
HC-UFS43
HC-SFS52
MR-J2S-60CL
HC-SFS53
HC-KFS73
MR-J2S-70CL
HC-MFS73
HC-UFS72 73
HC-SFS81
MR-J2S-100CL
HC-SFS102 103
HC-SFS121
HC-SFS201
HC-SFS152 153
MR-J2S-200CL
HC-SFS202 203
HC-RFS103
HC-RFS153
HC-UFS152
HC-SFS301
HC-SFS352 353
MR-J2S-350CL
HC-RFS203
HC-UFS202
HC-SFS502
HC-RFS353
MR-J2S-500CL
HC-RFS503
HC-UFS352
HC-UFS502
MR-J2S-700CL
HC-SFS702
Note: 1. Note that the power supply capacity will vary according to the power supply impedance. This value assumes that the power
factor improving reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the
regenerative brake option, use Equation 14.1 in Section 14.1.1.
(Note 1)
Servo amplifier-generated heat [W]
Power supply
capacity [kVA]
At rated torque
0.3
25
0.3
25
0.3
25
0.5
25
0.5
25
0.5
25
0.9
35
0.9
35
0.9
35
1.0
40
1.0
40
1.3
50
1.3
50
1.3
50
1.5
50
1.7
50
2.1
90
3.5
90
2.5
90
3.5
90
1.7
50
2.5
90
2.5
90
4.8
120
5.5
130
3.5
90
3.5
90
7.5
195
5.5
135
7.5
195
5.5
195
7.5
195
10.0
300
13 - 2
(Note 2)
Area required for heat dissipation
At servo-off
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
15
20
20
20
20
20
20
25
25
25
25
25
25
[m
2
]
[ft
2
]
0.5
5.4
0.5
5.4
0.5
5.4
0.5
5.4
0.5
5.4
0.5
5.4
0.7
7.5
0.7
7.5
0.7
7.5
0.8
8.6
0.8
8.6
1.0
10.8
1.0
10.8
1.0
10.8
1.0
10.8
1.0
10.8
1.8
19.4
1.8
19.4
1.8
19.4
1.8
19.4
1.0
10.8
1.8
19.4
1.8
19.4
2.7
29.1
2.7
29.1
1.8
19.4
1.8
19.4
3.9
42.0
2.7
29.1
3.9
42.0
3.9
42.0
3.9
42.0
6.0
64.6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents