Tripoli Screen Door - Regency P36E-NG4 Owners & Installation Manual

P36e zero clearance direct vent gas fireplace
Table of Contents

Advertisement

REGENCY
OPTIONS
®
When installing the optional Tripoli Screen Door Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm)
on each side must be used (see Diagram 1).
The Tripoli Screen Door Series also requires steel stud framing above and on each side of the unit (refer to Diagram 1).
Framing & Mantle/Side Materials
Non - Combustible
Steel
Stud
Min. 6"
(153mm)
Diagram 1
Steel
Stud
Option #1:
Fireplace with 1-1/2" (38mm) Facing Material
The hearth material must be brought past the Tripoli frame all the way to the unit
face, so there will be no gap between the face and the actual fi replace.
* 'D' is Minimum height to combustible materials including the Minimum 2" (51mm) Top clearance to the Horizontal Vent.
P36E-4 Zero Clearance Direct Vent Gas Fireplace

TRIPOLI SCREEN DOOR

Arch Screen
Material
36-1/4"
(921mm)
Steel
Min. 6"
Stud
(153mm)
INSTALLATION NOTE:
FRAMING DIMENSIONS
OPTIONS
A
1
36-1/4"
(921mm)
(921mm)
2
36-1/4"
(921mm)
(921mm)
Steel
Steel
Stud
Stud
Fireplace with 1" (25mm) Facing Material
P36E
B
C
36-1/4"
14-1/4"
46"*
(362mm)
(1168mm)
36-1/4"
13-3/4"
46"
(349mm)
(1168mm)
Option #2:
D
Steel
Stud
61