Terminal Dimensions and Torque Specs

The terminal screw dimensions for all WJ200 inverters are listed in table below. This
information is useful in sizing spade lug or ring lug connectors for wire terminations.
WARNING: Tighten the screws with the specified torque in the table below. Check for
any loosening of screws. Otherwise, there is the danger of fire.
WJ200 - 001S,002S,004S
WJ200 - 001L,002L,004L,007L
WJ200 - 007S,015S,022S
WJ200 - 015L,022L,037L
WJ200 - 004H,007H,015H,022H,030H,040H
WJ200 - 055L,075L
WJ200 – 055H,075H
WJ200 - 110L
WJ200 - 110H,150H
WJ200 - 150L
Types
Screw
Width
Diameter
(mm)
M3.5
7.6
M4
10
M5
13
M6
17.5
M8
23
2−17
Tightening Torque
(N•m)
1.0
1.4
3.0
3.9 to 5.1
5.9 to 8.8