Configuring The Fcs Bit Error Rate Alarm; Setting The Fcs Error Threshold; Setting The Fcs Error Hysteresis Threshold - Cisco IE-3000-8TC Software Configuration Manual

Software configuration guide
Hide thumbs Also See for IE-3000-8TC:
Table of Contents

Advertisement

Configuring IE 3000 Switch Alarms
Before you use the notifies command to send alarm traps to an SNMP server, you must first set up the
Note
SNMP server by using the snmp-server enable traps alarms global configuration command. See the
"Enabling SNMP Traps" section on page
Use the no alarm facility temperature secondary to disable the secondary temperature alarm.
This example sets the secondary temperature alarm to the minor relay, with a high temperature threshold
value of 113
SNMP server.
Switch(config) # alarm facility temperature secondary high 45
Switch(config) # alarm facility temperature secondary relay minor
Switch(config) # alarm facility temperature secondary syslog
Switch(config) # alarm facility temperature secondary notifies
This example sets the first (primary) temperature alarm to the major relay. All alarms and traps
associated with this alarm are sent to a syslog server.
Switch(config) # alarm facility temperature primary syslog
Switch(config) # alarm facility temperature primary relay major

Configuring the FCS Bit Error Rate Alarm

This section describes how to configure the FCS bit-error rate alarm on your switch:

Setting the FCS Error Threshold

The switch generates an FCS bit error-rate alarm when the actual rate is close to the configured rate. Use
the fcs-threshold interface configuration command to set the FCS error threshold.
Beginning in privileged EXEC mode, follow these steps to set the bit error-rate value for a port:
Command
Step 1
configure terminal
Step 2
interface interface-id
Step 3
fcs-threshold value
Step 4
end
Step 5
show fcs-threshold
Step 6
copy running-config startup-config (Optional) Save your entries in the configuration file.
Use the no fcs-threshold interface configuration command to return to the default FCS threshold value.
Cisco IE 3000 Switch Software Configuration Guide
3-8
o
o
F (45
C). All alarms and traps associated with this alarm are sent to a syslog server and an
Setting the FCS Error Threshold, page 3-8
Setting the FCS Error Hysteresis Threshold, page 3-9
Purpose
Enter global configuration mode.
Enter the interface to be configured, and enter interface configuration mode.
Set the FCS error rate.
For value, the range is 6 to 11 to set a maximum bit error rate of 10
By default, the FCS bit error rate is 10
Return to privileged EXEC mode.
Verify the setting.
Chapter 3
3-11.
-8
.
Configuring Cisco IE 3000 Switch Alarms
-6
to 10
OL-13018-03
-11
.