Connecting Online - Omron ZEN-SOFT01-V4 - 12-2008 Operation Manual

Zen support software
Table of Contents

Advertisement

Connecting Online

3-2

Connecting Online

1,2,3...
44
Specifications Changes from Version 3.0 Support Software
Modem-related settings (Modem, Local information, Connect to)
that could not be used have been deleted.
3.
Click the OK Button to save the settings in the project.
Click the Cancel Button to discard the settings.
Click the Defaults Button to return to the default settings.
Check communications with the ZEN before transferring or verifying
programs. Connect the computer to the ZEN and perform the check
operation with the project file open.
1.
Select File(F)/Properties from the Menu Bar and make the ZEN
model and Expansion I/O Units 1 to 3 settings in the Properties
Dialog Box to match the system configuration of the ZEN to be
connected online.
2.
Turn OFF the ZEN power, connect the ZEN to the computer with
the Computer Connecting Cable, then turn ON the ZEN power
again.
When using a ZEN that supports external communications, a
confirmation message that says, "RS-485 will stop. Y/N" will be
displayed on the ZEN when you turn ON the power. Select Yes,
then click the OK Button
3.
Open the project file. Click the Go Online Button on the Toolbar
or select ZEN(Z)/Go Online/Offline(W) from the Menu Bar. A
confirmation dialog box will be displayed. Click the OK Button.
4.
Check that the Status Bar display has changed from Offline to
Online. The background color for the ladder view area will change
to gray when the ZEN is online.
Click the Go Online Button on the Toolbar again or select
ZEN(Z)/Go Online/Go Offline(W) from the Menu Bar. The
display on the Status Bar will return from Online to Offline. The
background color for the ladder view area will change back to
white.
Section 3-2