Omron TJ2-MC64 Hardware Reference Manual page 123

Trajexia machine control system
Hide thumbs Also See for TJ2-MC64:
Table of Contents

Advertisement

Hardware reference
Rotary switch
The rotary switch (SW1) sets the MECHATROLINK-II address that identifies
the GRT1-ML2 in the MECHATROLINK-II network. The settings range is
from 0 hex to F hex.
To set the MECHATROLINK-II address of the GRT1-ML2, do these steps:
1. Turn off the Unit power supply of the GRT1-ML2.
Note
The address of the GRT1-ML2 is read only at power on. Setting
the new address when the power is on has no effect.
2. To set the address of the unit, set communication dipswitch 1 and the
rotary switch as given in the table below.
/i
Dipswitch 1
Rotary
Address
switch
OFF
0
60 hex
OFF
1
61 hex
OFF
2
62 hex
OFF
3
63 hex
OFF
4
64 hex
OFF
5
65 hex
OFF
6
66 hex
OFF
7
67 hex
OFF
8
68 hex
OFF
9
69 hex
OFF
A
6A hex
OFF
B
6B hex
OFF
C
6C hex
OFF
D
6D hex
OFF
E
6E hex
HARDWARE REFERENCE MANUAL
Dipswitch 1
Rotary
Address
switch
ON
0
70
ON
1
71
ON
2
72
ON
3
73
ON
4
74
ON
5
75
ON
6
76
ON
7
77
ON
8
78
ON
9
79
ON
A
7A
ON
B
7B
ON
C
7C
ON
D
7D
ON
E
7E
118