Hardware reference
To use the F7 or G7 Inverter with the MECHATROLINK-II interface it is
necessary to make the following settings in the Inverter:
B1-01=3 Sequence via MECHATROLINK-II
B1-02=3 Reference via MECHATROLINK-II
Check the corresponding manual for details about the F7 or G7 Inverter.
Related BASIC commands
The following BASIC commands are related to the MECHATROLINK-II
Inverters F7 and G7 series:
ATYPE (ATYPE=49)
INVERTER_COMMAND
INVERTER_READ
INVERTER_WRITE
For more information, refer to the Trajexia Programming Manual.
3.5.13 MECHATROLINK-II repeater
The FNY-REP2000 is a MECHATROLINK-II repeater. It extends the range
and the maximum number of MECHATROLINK-II devices in the
MECHATROLINK-II network.
/i
Terminal/LED
Label
A
TX1
B
TX2
C
POWER
D
SW
E
CN1 & CN2
F
CN3
HARDWARE REFERENCE MANUAL
Description
CN1 communication indicator
CN2 communication indicator
Power indicator
Dipswitch
MECHATROLINK-II connectors
Power supply connector
fig. 52
B
F
E
D
C
A