Omron H5CX Manual page 5

Digital timer h5cx series
Hide thumbs Also See for H5CX:
Table of Contents

Advertisement

Characteristics
Item
Power-ON start: ± 0.01% ± 50 ms max. Rated against set value
Accuracy of operating time
and setting error (including
Signal start: ± 0.005% ± 30 ms max. Rated against set value
temperature and voltage in-
Signal start for transistor output model: ± 0.005% ± 3 ms max. (See note 2.)
fluences) (See note 1.)
If the set value is within the sensor waiting time at startup the control output of the H5CX will not turn ON until the
sensor waiting time passes.
100 M W min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and
Insulation resistance
between non-continuous contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
1,000 VAC (for H5CX-@SD), 50/60 Hz for 1 min between control output, power supply, and input circuit (2,000 VAC
for models other than H5CX-@SD)
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC
1.5 kV for 24 VAC/12 to 24 VDC
± 1.5 kV (between power terminals) and ± 600 V (between input terminals), square-wave noise by noise simulator
Noise immunity
(pulse width: 100 ns/1 m s, 1-ns rise)
Static immunity
Destruction: 15 kV
Malfunction: 8 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in three directions, four cycles each (8 min per cycle)
Malfunction: 10 to 55 Hz with 0.35-mm single amplitude each in three directions, four cycles each (8 min per cycle)
Shock resistance
Destruction: 294 m/s
Malfunction: 98 m/s
Life expectancy
Mechanical: 10,000,000 operations min. (under no load at 18,000 operations/h)
Electrical:
Approved safety standards
UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14, conforms to EN61812-1 (Pollution
(See notes 3 and 4.)
degree 2/overvoltage category III)
Conforms to VDE0106/P100 (finger protection).
EMC
(EMI)
Emission Enclosure:
Emission AC mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Conducted
Disturbance:
Immunity Burst:
Immunity Surge:
Immunity Voltage Dip/Interruption EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Degree of protection
Panel surface: IP66 and NEMA4 (indoors), and UL Type 4X (indoors) (See note 4.)
Weight
H5CX-A@: Approx. 135 g, H5CX-A11@/-L8@: Approx. 105 g
Note 1. The values are based on the set value.
2. The value is applied for a minimum pulse width of 1 ms.
3. To meet UL listing requirements with H5CX-L8@/-A11@ models, an OMRON P2CF-08-@ or P3G-08 Socket must be mounted on the Timer.
Otherwise, H5CX-L8@/-A11@ models are considered to meet UL508 recognition requirements.
4. The Y92S-29 Waterproof Packing and Y92F-30 Flush Mounting Adapter are necessary to ensure IP66, NEMA4, and UL Type 4X water-
proofing between the H5CX and installation panel.
2
each in three directions
2
each in three directions
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
See Life-test Curve on page 6.
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
EN61000-4-2:
EN61000-4-3:
EN61000-4-6:
EN61000-4-4:
EN61000-4-5:
H5CX-A@/-A11@/-L8@
6 kV contact discharge (level 2)
8 kV air discharge (level 3)
10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz ± 5 MHz) (level 3)
10 V (0.15 to 80 MHz) (level 3)
2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
1 kV line to lines (power and output lines) (level 3);
2 kV line to ground (power and output lines) (level 3)
Multifunction Digital Timer
H5CX-A/-L
5