Characteristics
Item
Power-ON start: ± 0.02% ± 0.05 s max. Rated against set value
Accuracy of operating time
and setting error (including
Signal start (minimum pulse width of 20 ms): ± 0.01% ± 0.03 s max. Rated against set value
temperature and voltage in-
Signal start (minimum pulse width of 1 ms): ± 0.01% ± 3 ms max.
fluences) (See note 1.)
If the set value is within the sensor waiting time at startup the control output of the H5CX will not turn ON until the
sensor waiting time passes.
100 M W min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts
Insulation resistance
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
1,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuit
Impulse withstand voltage
1.0 kV (between power terminals)
1.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
± 480 V (between power terminals) and ± 600 V (between input terminals), square-wave noise by noise simulator
Noise immunity
(pulse width: 100 ns/1 m s, 1-ns rise)
Static immunity
Destruction: 15 kV
Malfunction: 8 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in three directions, four cycles each (8 min per cycle)
Malfunction: 10 to 55 Hz with 0.35-mm single amplitude each in three directions, four cycles each (8 min per cycle)
Shock resistance
Destruction: 294 m/s
Malfunction: 98 m/s
Approved safety
UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14, conforms to EN61812-1 (Pollution
standards (See note 2.)
degree 2/overvoltage category III)
Conforms to VDE0106/P100 (finger protection).
EMC
(EMI)
Emission Enclosure:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Conducted
Disturbance:
Immunity Burst:
Immunity Surge:
Degree of protection
Panel surface: IP66 and NEMA4 (indoors), and UL Type 4X (indoors) (See note 2.)
Weight
Approx. 140 g
Note 1. The values are based on the set value.
2. The Y92S-29 Waterproof Packing and Y92F-30 Flush Mounting Adapter are necessary to ensure IP66, NEMA4, and UL Type 4X water-
proofing between the H5CX and installation panel.
Inrush Current (Reference Values)
Voltage
Applied voltage
12 to 24 VDC 26.4 VDC
38
2-stage Digital Timer
2
each in three directions
2
each in three directions
EN61812-1
EN55011 Group 1 class A
EN61812-1
EN61000-4-2:
EN61000-4-3:
EN61000-4-6:
EN61000-4-4:
EN61000-4-5:
Inrush current
Time
(peak value)
6 A
1.2 ms
H5CX-B
H5CX-BWSD
6 kV contact discharge (level 2)
8 kV air discharge (level 3)
10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz ± 5 MHz) (level 3)
10 V (0.15 to 80 MHz) (level 3)
2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
1 kV line to lines (power and output lines) (level 3);
2 kV line to ground (power and output lines) (level 3)