Operation Functions - Omron H5F Datasheet

Digital daily time switch
Hide thumbs Also See for H5F:
Table of Contents

Advertisement

Operation Functions

Timer operation (ON/OFF operation)
ON time
OFF time
Pulse-output operation
Pulse width
ON time
Forced ON/OFF operation
Override and automatic return operation
Regular
program
Output
operation
Start of override and
automatic return operation
Partial operation on specified day
Program 1
Program 2
(special)
Regular
program
Operation on
operation day
Operation on
specified day
Holiday setting
Operation on
Operation
operation day
on holiday
Regular
program
Operation in
present week
Operation from
next week
Note: Both the timer operation and the pulse-output operation cannot be programmed together.
Operation When Power Turns OFF
1. The time and settings are backed up using a lithium battery.
2. The display stays ON but the output turns OFF.
3. Settings for all types of operation except override and automatic
return operation are possible.
4
Digital Daily Time Switch
Controls the output according to preset of ON and OFF times
• Minimum setting unit: 1 min
• Up to 12 ON/OFF operations are possible per day.
Output turns ON for a fixed period (pulse width) at the set time.
• Pulse width: 1 to 59 s, or 1 to 60 min. (The same pulse width setting is used for all types of
output operation.)
• The pulse width can be set in units of 1 s or 1 min.
• Up to 24 pulse-output operations are possible per day.
Forcibly turns ON/OFF the output by the output ON/OFF switch.
Using the output ON/OFF switch and the Write Key, control output is held in the ON state until
the next OFF time.
• It is also possible to hold the control output in the OFF state until the next ON time.
• Operation after the output turns OFF (or ON) will be based on the regular program.
• This function can be used with pulse-output operation.
The Time Switch operates according to only some of the programs on a user-specified day.
(Convenient, for example, for executing a half-day operation on Saturday.)
• It is not possible to set operation to be executed only on the specified day.
• This function can be used with pulse-output operation.
It is possible to set a day in the present week as a holiday (i.e., a non-operation day: output
OFF regardless of the settings). When that day has passed, operation will continue according
to the regular program, and operation will be executed as normal on that day from the follow-
ing week
• This function can be used with pulse-output operation.
H5F

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

H5f-bH5f-fbH5f-kb