Holiday Setting Function
The following example shows how to stop operation for a certain day
in the present week and restore normal operation from the following
week using the holiday setting function.
Example: Stopping operation for Friday and Saturday in
the current week and resuming normal
operation from the following week
1. Press the
Key for 2 s min.
HOLIDAY
in run mode to enter holiday setting
mode. hday will flash and the oper-
ation day indicator (
) will light
under the days set for operation
day.
2. Move the
symbol to Friday using
Key. Clear the operation day
d
indicator (
) by pressing the
Key. Repeat the procedure
WRITE
for Saturday. (Press the
WRITE
again to clear the holiday setting.)
3. Press the
Key. The Time
HOLIDAY
Switch will enter run mode and the
operation day indicator under the
days set as holidays will turn OFF.
(When a day set as a holiday has
passed, the (
) indicator under
that day will automatically turn ON
again.)
Note: 1. Any day in the 7-day period starting from the present day
can be set as a holiday.
2. Operation based on the new settings (i.e., including the
holiday setting) will start as soon as the Time Switch re-
turns to run mode.
3. Holiday setting mode can be entered from run mode only.
4. If the present day setting in time adjustment mode is
changed, all holiday settings will be cleared.
5. If a day set as a holiday is changed in operation date set-
ting mode, the holiday setting for that day will be cleared.
Summer Time (DST) Function
The summer time function allows the Time Switch to be used in
regions that observe daylight saving time during the summer.
Each time the
Key is pressed in run mode, the present time
+1h
will switch between the (standard) present time and the present time
+ 1 hour (summer time).
SU MO TU WE TH FR SA
3 30
PM
ON
5 15
PW
PM
Note: 1. The summer time indicator (
summer time is set.
2. The contents of the programs are not changed.
3. The summer time setting can only be set or cleared in run
mode.
14
Digital Daily Time Switch
The color indicates flashing
SU MO TU WE TH FR SA
ON
hd ay
PW
SU MO TU WE TH FR SA
Key
ON
hd ay
PW
SU MO TU WE TH FR SA
10 30
AM
ON
5 15
PW
PM
The color indicates flashing
SU MO TU WE TH FR SA
4 30
+1h
PM
ON
5 15
PW
PM
) is displayed while
+1h
H5F
Switching between 12-hour (am/pm)
and 24-hour Display
Each time the
time display switches between 12-hour (am/pm) and 24-hour display.
12-hour (am/pm) Display
SU MO TU WE TH FR SA
3 30
PM
ON
5 15
PW
PM
Note: 1. Switching is possible only in run mode.
2. The factory setting is 12-hour (am/pm) display.
Override and Automatic Return
Operation
Override and automatic return operation can be used to handle sud-
den schedule changes without making changes to the program. The
output status can be set to ON or OFF directly using the output ON/
OFF switch. This output status is then held until the next ON/OFF
operation time.
Example 1: Starting operation earlier than the scheduled
time on the present day only
Regular setting:
Use the following procedure to start operation at 7:00 am
for the present day only.
Present day
7:00 am
Regular
program
8:30 am 5:15 pm 8:30 am 5:15 pm
Override and
automatic return
operation ON
Output
7:00 am
1. Change the setting of the output ON/OFF switch from AUTO to
ON.
2. Return the setting of the output ON/OFF switch from
ON to AUTO while holding down the
The ON state will be held from the point at which this
operation is performed (indicated by the arrow) until
the next (regular) OFF time.
Example 2: Stopping operation earlier than the
scheduled time on the present day only
Regular setting:
+1h
Use the following procedure to stop operation at 3:00 pm
for the present day only.
Present day
Regular
program
8:30 am
Override and
automatic return
operation ON
Output
8:30 am
Key is pressed for 2 s min. in run mode, the
h
SU MO TU WE TH FR SA
h
(2 s min.)
ON
PW
ON at 8:30 am; OFF at 5:15 pm
Next day
5:15 pm
8:30 am
5:15 pm
From the next day, output
operates according to the
regular program.
WRITE
ON at 8:30 am; OFF at 5:15 pm
Next day
3:00 pm
5:15 pm
8:30 am
5:15 pm
3:00 pm
8:30 am
5:15 pm
From the next day, output
operates according to the
regular program.
24-hour Display
The color indicates flashing
15 30
17 15
Switch
Key.
ON
AUTO
OFF

Hide quick links: