Omron CPM1A Operation Manual page 90

Sysmac series programmable controllers
Hide thumbs Also See for CPM1A:
Table of Contents

Advertisement

Wiring and Connections
!
Caution
Output Wiring Precautions
CPM1A-8ET1
24 VDC
24 VDC
Double-check the polarity of the power supply for the load before turning it on.
Observe the following precautions to protect the PC's internal components.
Output Short Protection
The output or internal circuitry might be damaged when the load connected to an
output is short-circuited, so it is recommended to install a protective fuse (0.5 to
1.0 A) in each output circuit.
Polarity of Power Supply for the Load
Double-check the polarity of the DC power supply for the load before wiring the
transistor output. If the polarity of the power supply is reversely connected, the
load will malfunction and internal components may be damaged.
+10%
/
–15%
COM
01
03
00
02
04
06
COM
05
07
+10%
/
–15%
Section 3-4
67