Wiring and Connections
Crimp Connectors
Caution
!
60
2. Average rectified current must be 1 A.
Always use crimp connectors for the CPM1A's power lines and I/O lines or else
use a solid wire (instead of a stranded wire). Do not connect bare stranded wires
directly to terminals. Bare stranded wires connected directly to the terminal can
cause a fire.
Use M3 terminal screws and tighten the screws securely (0.5 N S m).
6.2 mm max.
The recommended wire size for solid wires is 0.4 to 1.2 mm (AWG26 to AWG18).
IN
Diode
CPM1A
COM
Fork terminal
6.2 mm max.
Section 3-4
Ring terminal