Reading Status (C = 0001 hex)
Port and mode
Pulse output
High-speed counter input
PWM(891) output
Reading the Results of Range Comparison
(C = 0002 hex)
If C is 0002 hex, PRV(881) reads the results of
range comparison and stores it in D as shown in
the following diagram.
Reading Pulse Output or High-speed Counter Frequency (C = 00
If C is 00@3 hex, PRV(881) reads the frequency being output from pulse output 0 or 1 or the frequency
being input to high-speed counter 0 and stores it in D and D+1.
0000 or 0001 hex (Reading the frequency of pulse output 0 or 1)
0000 0000 to 0001 86A0 hex (0 to 100,000)
0010 hex (Reading the frequency of high-speed counter 0)
Counter input method: Any input method other than 4 differential phase mode:
Result = 00000000 to 000186A0 hex (0 to 100,000)
Note If a frequency higher than 100 kHz has been input, the output will remain at the maximum value of 000186A0
hex.
Counter input method: 4 differential phase mode:
Result = 00000000 to 00030D40 hex (0 to 200,000)
Note If a frequency higher than 200 kHz has been input, the output will remain at the maximum value of
00030D40 hex.
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Operation
The pulse output status is stored in D.
The high-speed counter status is
stored in D.
The PWM(891) output is stored in D.
Results of reading
15
0
D 0 0 0 0 0 0 0 0
Pulse Output Status Flag
OFF: Constant speed
ON: Accelerating/decelerating
PV Overflow/Underflow Flag
OFF: Normal
ON: Error
Pulse Output Amount Set Flag
OFF: Not set
ON: Set
Pulse Output Completed Flag
OFF: Output not completed
ON: Output completed
Pulse Output In-progress Flag
OFF: Stopped
ON: Outputting
No-origin Flag
OFF: Origin established
ON: Origin not established
At-origin Flag
OFF: Not stopped at origin
ON: Stopped at origin
Pulse Output Stopped Error Flag
OFF: No error
ON: Pulse output stopped due to error
15
0
D 0 0 0 0 0 0 0 0 0 0 0 0 0 0
15
0
D 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
15
D 0 0 0 0 0 0 0 0
@
3. Instructions
Comparison In-progress Flag
OFF: Stopped
ON: Comparing
PV Overflow/Underflow Flag
OFF: Normal
ON: Error
Pulse Output In-progress Flag
OFF: Stopped
ON: Outputting
0
Comparison Result 1
OFF: Not in range ON: In range
Comparison Result 2
OFF: Not in range ON: In range
Comparison Result 3
OFF: Not in range ON: In range
Comparison Result 4
OFF: Not in range ON: In range
Comparison Result 5
OFF: Not in range ON: In range
Comparison Result 6
OFF: Not in range ON: In range
Comparison Result 7
OFF: Not in range ON: In range
Comparison Result 8
OFF: Not in range ON: In range
3 hex)