Using TPO(685) Alone
When CIO 0.00 is ON, TPO(685) takes the duty ratio in D10, converts the duty ratio to a time-
proportional output, and outputs the pulses to CIO 100.
In this case, the control period is 1 s and the output limit function is enabled with a lower limit 20.00%
and an upper limit of 80.00%.
0.00
TPO
S
C
R
CS/CJ/NSJ Series Instructions Reference Manual (W474)
TPO(685) takes the duty ratio in D10, converts that
duty ratio to a time-proportional output, and outputs
D10
Duty ratio
the pulse output to bit 00 of CIO 1.
D0
Parameters
1.00
Pulse output
D0
1
1
0
0
D1
0
0
6
4
D2
0
7
D
0
D3
1
F
4
0
D4
Do not set.
D5
Do not set.
D6
Do not set.
:
:
D10
0 to 2710 hex
Duty ratio input, read initial value, and enable output limit function.
Control period = 1.00 s
Output lower limit = 20.00%
Output upper limit = 80.00%
0 to 100.00%