Master Drives
CBD
01/23/98
5.2.3

Other CBD-relevant parameters

...Section, Start-up / parameterization "Expert application" of the drive Instruction Manual
Change process
data wiring ?
no
Connect receive
channel:
- control words
- setpoints
Connect response
channel:
- status words
- actual values
Other CBD
relevant
parameters
Continue in the Section, Start-up / parameterization "Expert application" of the drive Instruction Manual.
Fig. 5.7
Optional parameters
♦ "CB/TB TLg OFF Time"
"CB/TB TLg OFF Time"
Using parameter "CB/TB TLg OFF Time" (also refer to the drive Instruction Manual, Section "Parameter list")
you can define whether the process data entered by CBD in the dual port RAM is monitored by the drive. The
parameter value of this parameter corresponds to the telegram failure time in ms. The parameter pre-assignment
value is 10 ms, i. e. a maximum of 10 ms can lie between 2 received process data DeviceNet™ messages,
otherwise the drive shuts down with fault F082. The monitoring is disabled for a parameter value of 0.
The drive monitors process data entry into the dual port RAM from the instant when CBD enters process data
into the dual port RAM for the first time after power-up of the drive. Fault F082 can only be initiated from this time
instant onwards!
PZD data can be sent by DeviceNet™ I/O (both Bit Strobe and Poll) messages. PZD data can also be sent by
DeviceNet™ explicit messages using the assembly class. PKW requests sent by explicit messages using the
PKW object (see previous Parameter area (PKW) section 4.2) do not update the PZD information and do not
affect this drive telegram monitoring function.
46
5 Start-up
5.2 Process data combination
5.2.3 Other CBD-relevant parameters
yes
Refer to Section 4.3.1
Refer to Section 4.3.2
Refer to Section 4.3.3
Telegram failure time
CUVC & CUMC
P722.x
DC-Master
CU2
U722.x
P695