MASTER SETTINGS PROGRAMMING
continued
Adjusting Regeneration settings will turn any set
CAUTION
relays off. Any required relays will need to be
reprogrammed in the Relay Output screen.
• regen flow: Contains settings for the type of regenerant
flow to be used in the valve. Changes to this setting
affects the cycle steps displayed in the Regeneration
Cycle Wheel on the Home screen. Regenerant flow cycle
steps are described below. See TOUCHSCREEN CONTROL
FEATURES for cycle step definitions.
• downflow: Cycle steps are as follows: Backwash, Draw,
Rapid Rinse, Tank Refill
• upflow: Cycle steps are as follows: Draw, Backwash,
Rapid Rinse, Tank Refill
• downflow 2X backwash: Cycle steps are as follows:
Backwash, Draw, Backwash, Rapid Rinse, Tank Refill
• custom upflow / downflow / filter: Allows for up to 20
programmable cycle steps.
• variable refill: (softener delayed only) Cycle steps
are as follows: Refill, Pause, Draw, Backwash, Rinse.
Variable refill calculates refill time based on salt
dosage, media volume, and BLFC size.
Relay Output Screen
From the main Master Settings screen (Figure 18) press the
relay button to display the Relay Outputs screen.
Figure 26 Relay Outputs Screen
• auxiliary 1 / auxiliary 2: Contains settings for
programming up to two auxiliary relay outputs. There are
three types of relays that can be programmed:
• Cycle Based: The relay will turn on when the valve
moves to the specified regeneration cycle steps. To
program, select each cycle step button for which the
relay should turn on.
• Time Based: The relay will turn on and off at up to
two specified start and end times. If water saving
regeneration is on, this is not an available option.
• Volume Based: The relay will turn on when the valve
has treated a specified volume of water. Duration can
be set for up to two hours.
• Alarm Based: The relay will turn on when the specified
alarm condition (or any alarm condition) is met. The
relay will turn off when the alarm is cleared.
14 • FLECK 5800 XTR2 Service Manual
Meter Screen
From the main Master Settings screen (Figure 18) press the
meter button to display the Meter screen.
Figure 27 Meter Screen
• meter type: Contains settings for the type of meter
installed with the system. The 5810/5812 valve uses an
internal 1.25" turbine meter.
• generic: A generic option is available if the installed
meter does not match any other selection. Requires
setting the number of pulses per volume to ensure proper
metering.
• emergency regen: When on, the emergency regen feature
causes a regen to occur immediately when 105% or
greater of the capacity (e.g., volume plus reserve) is used.
Continuous Flow Detect Screen
From the Master Settings screen (Figure 18) press
button to display the Continuous Flow Detect screen.
Figure 28 Continuous Flow Detect Screen
• continuous flow detect: When active, triggers an alarm
when continous flow of 0.5 GPM or 1 LPM is detected by
the flow meter over an 8-hour period.