Replacing the iRMC microSD card
▶ Remove the defective iRMC microSD card, see
microSD card" on page
CAUTION
(not valid for Europe, Middle East, India and Africa)
The iRMC microSD card contains customer information.
After removing the iRMC microSD card, hand the card over to
the customer.
If the customer requests disposal of the defective microSD card,
proceed as follows: Using a pair of side-cutting pliers, cut the
microSD card in half.
▶ Install the new iRMC microSD card, see
on page
234.
Concluding steps
"Installing a riser module" on page
"Installing the CX2550 M6 or CX2560 M6 server node" on page
▶ If applicable, reconnect all external cables.
"Switching on the server node" on page
"Enabling the boot watchdog" on page
▶ If applicable,
"Resuming BitLocker functionality" on page
10.6

M.2 SSD

10.6.1

Slots and bolts for M.2 SSDs

The system board offers two M.2 slots with support for 80 mm and 110 mm
long M.2 SSDs by using different latch locations. With the M.2 SSD an internal