Mid-Stop Limit
NOTE: Setting of the MID-STOP should only be performed AFTER the travel limits and max run timer settings have
been made.
1. If operator is in RUN mode, press CAL/RUN to enter CALIBRATION MODE.
2. Press the CLOSE key to close the door to the down limit.
3. Press SCROLL (up or down) until display reads MID-STOP > CLR. FIG.4
•
If display reads MID-STOP > SET, Press the SET/CLEAR key to reset to CLR.
4. Press the OPEN key to open door to desired height.
5. Press SET/CLEAR key to set mid-stop. Display will show MID-STOP > SET.
6. Press CAL/RUN key to return to RUN mode.
The MID-STOP feature must be turned off in order to properly set the Max Run Timer.
La fonction MID-STOP doit être désactivée afin de régler correctement la minuterie de course maximum.