Siemens MindConnect Nano System Manual page 60

Insights hub
Hide thumbs Also See for MindConnect Nano:
Table of Contents

Advertisement

Configuring protocols
4.4 Overview of Modbus TCP protocol for MindConnect Nano
Parameter
responseTimeout
responseSuspensionTime
requestDelay
Modbus TCP data point parameter
In order to collect the data of your Modbus TCP device, you must add new data points.
The following picture shows the data point parameter window:
The following table shows the parameter of the Modbus TCP data point window:
Parameter
Description
Data Type
Data type supported by backend (e.g. INT).
MindConnect Nano
System Manual 7/2023
Description
You can set the timeout interval used to wait for a response from the
Modbus device. If the waiting before receiving the response is longer than
the given timeout, an error will be generated. Range: 500ms (default) ...
60000ms
If a byte timeout or a response timeout was detected, then this waiting
time is added before the next request is started. During this time any
response from the Modbus device will be flushed. Range: 0ms ... 45000ms.
(default: 1000ms)
You can set the time between the response from the Modbus device and
the next request to this Modbus device. Range: 0ms (default) ... 10000ms
60