Troubleshooting
7.1 Troubleshooting
Error
Problem
- Although an asset
MindConnect
uploaded to Insights Hub
Nano L2 -
Monitor and Visual Analyzer.
ERROR LED
- MindConnect Nano cannot
onboard to Insights Hub
MindConnect
Nano L2-
Data loss
ERROR LED
blinking RED
MindConnect
Nano L2-
Firmware update error
ERROR LED
RED
MindConnect
Nano L3-
Onboarding failed
MAINT LED
ORANGE
MindConnect Nano
System Manual 7/2023
Possible cause
Possible remedy
- No connection
to data source
Check the connection between
- The address of
MindConnect Nano and data sources
the data point
(Plant Network ports and cables-
configuration can
S7/OPC UA Server)
be incorrect
- Check the connection between
- Incorrect asset
MindConnect Nano and data sources
configuration
(Plant Network ports and cables-
- Not
S7/OPC UA server)
accomplished
- Check data sources configuration.
asset
- Check configuration of each data
configuration
point.
(Network
- Check configuration of your asset
Connection)
- (Network Configuration).
Invalid ID of
- Check if MindConnect Nano ID is
MindConnect
correct.
Nano
MindConnect
Nano was offline
- Check outbound connection
for too long, so it
- Check Ethernet cables
could not send
- Check Proxy (IP address, User
data to Insights
Authentication can be required)
Hub and the
storage is full.
- Make sure that you are using the
- Technical
correct firmware type (MindConnect
problems with a
Nano).
new version of
- MindConnect Nano will automatically
firmware
restart and then firmware update will
- Incorrect
be carried out after a while.
firmware type
- If MindConnect Nano does not
- Certificate
restart automatically, then restart it
problems,
manually: by switching on and off the
Authentication
"power button" on MindConnect
problems etc.
Nano.
- Make sure that the data on the USB
stick still is valid. (The data, which you
exported to the USB stick, is still valid
- Configuration
only for 7 days.). If it is expired, use the
file on the USB
asset configuration to export a new
stick is invalid
valid configuration to your USB stick.
- Internal error
- Check asset configuration and
reconfigure, if it is required and export
a new configuration to USB stick.