If you only provide some of the above mentioned parameters, then the omitted
parameters will be ignored. This means that either the last restricted device
configuration of these parameters will be used, or they will be treated as not set.
To enable device configuration changes of specific parameters again, a JSON
command containing those parameters with value "false" can be provided via
USB stick.
To turn it off a new JSON command file needs to be provided with "false" for all
parameters.
Check network
Command description To find out, if the MindConnect device is successfully connected to
Insights Hub using the current onboarding configuration, a ConBox_Commands.json file
containing "CheckNetwork" command on an USB stick can be used. After the network analysis
has been performed, the analysis result will be written to the USB stick.
Depending on the current network situation, it might be possible that the execution of all
internally executed tests will take some minutes.
This command is available from the version MindConnect Nano firmware
V03.04.02.10 b003.
CheckNetwork command
Using following JSON command in a ConBox_Commands.json file, a network analysis will be
performed and the result will be written to the USB stick:
{
"Commands": [
{
"Cmd": "CheckNetwork",
"NetworkChecks": [
]
}
]
}
107
{
"CheckCloudConnection":
}
"true"
Troubleshooting
7.1 Troubleshooting
MindConnect Nano
System Manual 7/2023