The procedure for making up the cable is described below.
Also refer to this procedure for making a connecting cable for use with RS-422A/485 type connections.
Cable Preparation
The preparation of the cable differs according to whether or not the shielding wire is to be connected to the FG.
Cable with Shield Connected to FG
1. Cut the cable to the required length.
2. Remove the external vinyl insulation from the cable with a razor blade. Take care not to damage the
shielding underneath.
3. Cut back the shielding wire with scissors.
4. Use wire strippers to strip the insulation from each wire.
5. Fold back the shielding wire.
6. Wrap aluminum foil tape around the folded-back shielding wire.
Cable with Shield Not Connected to FG
1. Cut the cable to the required length.
2. Remove the external vinyl insulation from the cable with a razor blade. Take care not to damage the
shielding underneath.
3. Cut back the shielding wire with scissors.
4. Use wire strippers to strip the insulation from each wire.
Appendix D

Making the Cable

(1)
(2)
40 (1.57) (RS-232C)
25 (0.98) (RS-422A)
(3)
(4)
5
(0.19)
(5)
(6)
Units: mm (inch)
10
(0.39)
Aluminum foil tape
265