The following table provides a list of the programming options and their factory default settings.
Program Option
Detector Programming
Detector Type
Detector Verification
Detector Walktest
Detector PAS
Detector Presignal
Detector Zone Assign.
Detector Adj/Noun
Module Programming
Module Type
Module Walktest
Module Presignal
Module Zone Assign.
Module Adj/Noun
Module Control Module Delay
Module MNS Override
Message
Zone Type
Zone 000-255
Zone Installed
Special Purpose Zones 251-255
Loop Class
Loop Protocol
Loop 1 Installed
Loop 2 Installed
Loop 3 Installed
Trouble Reminder
Banner
Time Format
Hours Setting
Minutes Setting
Second Settings
AM-PM Setting
Month Setting
Day Setting
Year Setting
Daylight Savings
Month Start Daylight Savings
Week Start Daylight Savings
Month End Daylight Savings
Week End Daylight Savings
AC Loss Delay
PAS Timer
Presignal Timer
Waterflow Retard Timer
Control Module Delay Timer
NAC 1,2,3, & 4 Enable
NAC 1,2,3, & 4 Silenceable
NAC 1,2,3, & 4 Type
NAC 1,2,3, & 4 Sync Type
NAC 1,2,3, & 4 Autosilence
NAC 1,2,3, & 4 Coding
NAC 1,2,3, & 4 Zones
NAC 1,2,3, & 4 Silence Inhibit
NAC 1,2,3, & 4 MNS Override
NAC 1,2,3, & 4 MNS Active
Charger Enabled
4XTM Supervision
Remote Sync Enabled
136

Appendix B: Default Programming

Factory Default
Not Installed
Smoke-Photo
Off
Yes
No
No
000 only
none
Not Installed
Monitor
Yes
No
000 only
none
No
No
No Message
Monitor Zone
Enabled
000
Off
Class B
LITESPEED
Yes
No
No
24 Hr
12 Hr
01
00
00
AM
01
01
23
Enabled
March
Week 2
November
Week 1
2
0
0
0
0
Enabled
Yes
Synced Strobe
System Sensor
0
Steady
Zone 000 only
No
No
No
Yes
No
Yes
Program Option
Battery Size
Language
Aux Power 1 Class A
Aux Power 1 Resettable
Aux Power 2 Resettable
Aux Power 3 Resettable
Canadian Option
Waterflow Silenceable
Relay 1
Relay 2
Relay 3
Communicator Installed
POTS, Ethernet Enabled
Ethernet Location ID
Ethernet CS ID
POTS, Ethernet Account Code
POTS Enabled
POTS Type
POTS Supervised
Gains Dialing
Gains Reporting
DHCP Enabled
Trouble Report Limit
Report Style
Primary Account Code
Secondary Account Code
Test Time
Primary Phone Number
Secondary Phone Number
Primary Comm Format
Secondary Comm Format
ANN-Primary Enabled
ANN-Primary Modules Addr. 1 - 8
ANN-Secondary Enabled
ANN-Secondary Modules Addr. 1 - 8
ANN-S/PG Port
ANN-S/PG Baud
ANN-S/PG Data Bits
ANN-S/PG Parity
ANN-S/PG Stop Bits
ANN-S/PG Offline Timer
ANN-S/PG Printer Supervision
ANN-80/100 Piezo Enabled
ANN-80/100 Lock Enabled
ANN-80/100 Acknowledge Button Enabled
ANN-80/100 Silence Button Enabled
ANN-80/100 Reset Button Enabled
ANN-80/100 Drill Button Enabled
ANN-I/O Point/Zone
ANN-I/O Range
ANN-I/O Active LEDs Only
ANN-RLY Relay 1
................through.......................
ANN-RLY Relay 10
ANN-LED Point/Zone
ANN-LED Alarms/ATS (Alarm, Trbl, Supv)
ANN-LED Range
F1 - F4 function keys
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Factory Default
12-30AH
English
No
No
No
No
Off
No
Alarm
Trouble (fixed)
Supervisory
No
No
0000
0000
000000
No
Touchtone
No
Normal
Normal
Yes
0
Point
000000
000000
0100
Ademco Contact ID
Ademco Contact ID
No
None
No
None
Serial
9600
7
Even
1
N/A
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Zone
00-29
Zone 1
............
Zone 10
Zone
ATS
0 - 9
Disabled