Master Programming Level
The LED assignments for the modules annunciating Point Ranges 021-030, 031-040, 041-050, 051-060, 061-070, 071-080, 081-090, 091-
100, 101-110, 111-120, 121-130, 131-140, 141-150 and 151-159 will follow the same pattern as the second ANN-LED Module.
ANN-RLY Options
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #2
The ANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays Relays 1
through 3. Pressing the down arrow key will display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key corresponding to
the relay to be programmed. Following is a list of the available programming options for each relay:
Alarm
Supervisory
Supervisory AR
Trouble
Comm Fail
Process Mon
Process Mon AR
AC Loss
Hazard
Medical
Silenceable Alarm
Zone Active XXX (where XXX = programmed zone 000 to 255)
Carbon Monoxide
Auto-Configure
XXX ANN-BUS
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
(XXX) ANN-BUS Screen #1
process and cause the following screen to be displayed:
Class A
XXX ANN-BUS
1=CLASS A
ANN-BUS (XXX) Screen #2
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Point 016
Point 017
Active/Alarm
Active/Alarm
Point 016
Point 017
Trouble
Trouble
Point 016
Point 017
Supervisory
Supervisory
Table 3.11 ANN-LED Module #2 (Point Range 011 - 020)
Pressing 2 for Module Options while viewing the ANN-BUS Address Screen when the ANN-RLY option is
YES
selected, will cause the following screen to be displayed:
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS mod-
YES
ules online on the selected ANN-BUS. The software will search the selected circuit for all ANN-BUS modules
and automatically program the device type and address into the system. For the Auto-Configure to work, the
selected ANN-BUS must be enabled, the annunciators must be connected/powered, and a unique address must
be set on each annunciator. Pressing 3 while viewing ANN-BUS (X) Screen #1 will begin the Auto-Configure
This option applies to the Primary ANN-BUS only. The primary ANN-BUS can be configured for Class A wir-
NO
ing. If wired in Class A configuration, press 1 on ANN-BUS Primary Screen #2 to select Class A Yes. Each
press of the 1 key toggles between Class A No and Class A Yes.
Point 018
Active/Alarm
Point 018
Trouble
Point 018
Supervisory
ANN-RLY - ADDR. X-1
1=RLY 1
ZONE 000
2=RLY 2
ZONE 001
3=RLY 3
ZONE 002
ANN-RLY Options Screen
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
Point 019
Point 020
Active/Alarm
Active/Alarm
Point 019
Point 020
Trouble
Trouble
Point 019
Point 020
Supervisory
Supervisory
Programming
93