Nacs (Notification Appliance Circuits) - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
Suite Resound (Canadian Mode Only)
TIMER
1=IN SUITE SIL.
2=SUITE RESOUND
Timer Screen #3
A flashing cursor will appear in the lower left corner of the display. Type the twp digit in suite silence delay in minutes (01 to 10 minute
delay). The default time is 1 minute. When the second digit is entered, the display will return to the Delay Screen which will indicate the new
delay time. The Suite Resound Timer starts when the In Suite Silence timer expires.

NACs (Notification Appliance Circuits)

SYSTEM SETUP
1=TIMERS
2=NACS
3=RELAYS
System Setup Screen #2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3, or 4 for NAC 4.
The following screens will be displayed for each selection:
NAC #
1=ENABLED
YES
2=TYPE SYNCED STROBE
3=SILENCEABLE
YES
NAC Screen #1
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board
NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
NOTE: The programming for NAC 1 will determine the operation of the remote power supply sync.
Type
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the dis-
play will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
The Suite Resound feature is only available when the FACP is in Canadian mode of operation. When enabled,
30
this feature will resound all outputs and NACs that were silenced by the In Suite Silence timer (if there is an
01
unacknowledged fire alarm on the panel) after a programmed length of time. Once the Suite Resound Timer
occurs, additional fire alarms on the system will not restart the In Suite Silence timer. Pressing 2 while viewing
Timer screen #3 will display the following.
The options for the NACs on the control panel main circuit board can be configure by pressing 2 while viewing
System Setup Screen #2. The following screens will be displayed:
NAC #
1=AUTO SILENCE
2=CODING
STEADY
NAC Screen #2
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1. The fol-
lowing screen will be displayed. Press the down arrow key to view additional screens:
NAC Type Code
Bell
None
Horn
None
Strobe
None
Synced Strobe
Synchronized to manufacturer
Strobe Sil Sync
Same as Synced Strobe but Silence turns off audible & visual devices
Blank
None
SUITE RESOUND
RANGE 1-10 MINUTES
In Suite Resound Screen
NACS
1=NAC 1
3=NAC 3
2=NAC 2
4=NAC 4
NAC Selection Screen
NAC #
1=ZONE ASSIGNMENT
00
000
2=SIL. INHIBIT
NAC Screen #3
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
Special Function
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
NO
3=MNS ACTIVE
NAC Screen #4
Programming
S
NO
NO
73