Programming
ZNNN - represents the first of five possible software zones that the detector is assigned to (NNN = the three digit zone number from
000 - 0255)
V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled)
W or * - indicates whether or not walktest is enabled (W = walktest enabled and * = walktest disabled)
X or * - indicates whether or not the detector is wireless (X = wireless detector and * = wired detector)
1D017 - represents the Loop, Device type and Device address (1=SLC Loop, D=Detector and 017=Detector Address 017)
The following examples show the editing of a photoelectric smoke detector with address 017, located on the SLC loop:
EDIT DETECTOR 1D017
2=TYPE SMOKE(PHOTO)
3=VERIFICATION
EDIT DETECTOR 1D017
2=SOUNDER BASE
3=NOT USED
Enabled/Disabled Detector
EDIT DETECTOR
ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Type
EDIT DETECTOR
ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Pressing the down arrow key will display additional detector types as indicated in the following table.
52
ENABLED
YES
OFF
Edit Detector Screen #2
WIRELESS
NO
Edit Detector Screen #5
The system will show whether the detector is enabled or disabled. To change the status of the detector, the pro-
YES
grammer must enter system programming using a Maintenance password.
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen #2.
YES
This will cause the control panel to display the following Detector Type Screens:
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
Detector Type
Smoke Photo
User-Defined-1
Smoke (Ion)
User-Defined-2
Heat
User-Defined-3
Smoke Duct-P
User-Defined-4
Photo w/Heat
User-Defined-5
CO Only
User-Defined-6
Duct Superv
User-Defined-7
Photo Super AR
User-Defined-8
CO Supervisory
User-Defined-9
ADAPT
User-Defined-10
Beam
User-Defined-11
EDIT DETECTOR 1D017
1=WALKTEST
YES
2=PAS
YES
3=PRE-SIGNAL
YES
Edit Detector Screen #3
EDIT DETECTOR 1D017
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Detector Screen #6
through
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
same as previous (Smoke Ion)
Fire Alarm
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke DuctP)
Fire Alarm
same as previous (Photo w/Heat)
CO Alarm
same as previous (CO Alarm)
Supervisory, latching
same as previous (Superv DuctP)
Supervisory, nonlatching (works only in LiteSpeed)
same as previous (Photo-SupervAR)
Supervisory, latching
same as previous (CO Supervisory)
Fire Alarm
same as previous (ADAPT)
Fire Alarm
same as previous (Beam)
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
EDIT DETECTOR 1D017
1=ZONE ASSIGNMENT
000
Edit Detector Screen #4
DETECTOR TYPE
1=USER-DEFINED-14
2=DET HIGH HEAT
3=USER-DEFINED-15