2: Autosilence Timer; 3: Trouble Reminder; 4: Waterflow Retard Timer; 5: Alarm Verification (None Or One Minute) - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Walktest

4.21.2 Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will automatically be silenced after a programmable dura-
tion of 5 to 30 minutes. Pressing the Drill key will restart the timer. Autosilence operation requires the approval of the local Authority Hav-
ing Jurisdiction.
4.21.3 Trouble Reminder
If selected, this feature causes a reminding 'beep' every 15 seconds during an alarm (after the Alarm Silence key is pressed) and every two
minutes during a trouble condition (after the Acknowledge/Step or Alarm Silence key is pressed). The 'beeps' from the onboard piezo
sounder will occur until the alarm or fault is cleared.
Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the trouble condition still exists.
4.21.4 Waterflow Retard Timer
If selected, this option will delay the activation of a waterflow type alarm for a programmable time duration from 1 to 90 seconds. This delay
is in addition to any time delay inherent in the waterflow device. This feature requires the approval of the local Authority Having Jurisdic-
tion.
4.21.5 Alarm Verification (None or One Minute)
If alarm verification is selected, an addressable smoke detector's alarm is ignored for a retard time of 13 seconds and the detector's alarm
condition is automatically reset. There will be no alarm indication at the FACP during the Retard period. A confirmation period of 60 sec-
onds follows, during which a subsequent alarm from the same detector will cause the panel to immediately activate the appropriate outputs
and indicate the alarm condition at the FACP. If a different detector alarms any time during the first detector's verification period, the panel
will immediately activate all appropriate outputs and indicate the alarm condition at the FACP. If no additional detector alarms occur within
73 seconds of the first alarm (13 second retard plus 60 second confirmation), the timer resets and the panel is ready to verify any new detec-
tor alarms which may occur. The following is a graphic representation of Alarm Verification.
Detector Alarm Verification
(Retard & Confirmation)
Detector Goes Into Alarm
Different Detector Alarms
During First Detector's
Verification Period
NOTE: Alarm Verification is available only for addressable smoke detectors, not conventional smoke detectors.
4.21.6 Control Module Delay Timer
The control module delay feature, if enabled, will delay activation of a control module after a programmed time of 1-180 seconds after being
triggered by an alarm condition. This feature requires the approval of the local Authority Having Jurisdiction. Refer to the table on page 43
for permissible settings.
4.22 Walktest
Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will momentarily sound the Notification
Appliance Circuits in the building and store the walktest information in a file at the panel. A silent walktest will not sound the NACs but will
store the walktest information in a file which can be viewed at the panel. Disabled NAC devices will not activate during walktest.
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed control outputs for four seconds, if those out-
puts have been programmed for silenceable activation. It also stores each alarm in the walktest history file which can be sent to an optional
printer. The stored display will be the same as if the device actually activated except the colon (:) in the time stamp is replaced with an aster-
isk (*).
Note that if the system under test includes one or more enabled MMF-302 monitor modules, the following may apply:
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
13 sec.
0 sec.
RETARD
Alarm Ignored
CONFIRMATION (60 seconds)
Control Panel Processes Alarm if Same Detector is Still in Alarm
Control Panel Immediately Processes Alarm
Operating Instructions
73 sec.
109