Honeywell Fire-Lite Alarms ES-1000X Manual page 31

Addressable fire alarm control panel
Table of Contents

Advertisement

Optional Module Installation
Exception: When using the ANN-RLY module, the installer must ensure that the maximum 24VDC power line drop does not exceed 0.3
volts. This results in the following wiring limitations:
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
3 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
The total worst case current is calculated as follows:
Wiring Configuration
Figure 2.15 illustrates the wiring between the FACP's Primary ANN-BUS and ANN-BUS devices.
Figure 2.16 illustrates the wiring between the FACP's Secondary ANN-BUS and ANN-BUS devices.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Wire Gauge
ANN-80 Current Draw
ANN-S/PG Current Draw
Total Worst Case Current Draw
ANN-BUS Device
Figure 2.15 Primary ANN-BUS wiring to ANN-BUS Device
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS Device
Figure 2.16 Secondary ANN-BUS wiring to ANN-BUS Device
Maximum Wire Length
18
16
14
12
= 3 X 0.040 amps
= 1 X.0.040 amps
ANN-BUS and power wiring are
supervised and power-limited
Primary
ANN-BUS
ES-1000X
Secondary
ANN-BUS
312 feet
497 feet
787 feet
1,250 feet
= 0.120 amps
= 0.040 amps
= 0.160 amps
24 VDC
non-resettable
24 VDC
non-resettable
ES-1000X
Installation
31