Honeywell Fire-Lite Alarms ES-1000X Manual page 63

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
The following table contains control module type codes and their functions which are displayed in the Control Type screens:
Silenceable
EDIT CONTROL
ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
Walktest
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
000
Edit Control Screen #3
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2 while viewing Edit Control Screen #3 displays
the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be
assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones can be
left blank or programmed as general alarm zones Z000. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Control Screen #3.
Adjective/Noun
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Control Screen #4
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Control Type
Bell Circuit
Horn Circuit
Sounder
Relay-1FC
Strobe Circuit
Control
Resettable Power
HVAC Shutdown RLY
HVAC Shutdown NAC
1
When using a control relay module to supply resettable power to
conventional 2-wire smoke detectors, the addressable monitor module
must be programmed for Smoke-Conventional operation
2
For HVAC SHUTDOWN description, refer to "Control Module
Operation" on page 143.
The Silenceable selection allows the programmer to select whether output devices connected to the control
YES
module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the 3
key while viewing Edit Control Screen #2 will enable the Silenceable feature causing the display to read
Silenceable Yes. Repeated presses of the 3 key will cause the display to toggle between Silenceable Yes and
Silenceable No. When set to Canadian mode of operation, a third silenceable type appears, Silenceable Auto.
When set to Auto, the control module will automatically silence after the Control Module Auto Silence timer
expires.
The Walktest feature allows one person to test the system devices without the necessity of manually resetting
the control panel after each device activation. To enable devices, which are connected to a control module, for
the Walktest feature, press 1 while viewing the Edit Control Screen #3 until the display reads Walktest Yes.
Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walk-
test" on page 109 for additional information.
Z000
The Adjective/Noun selection allows the programmer to enter specific descriptors about the control module
currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause the following screen
to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Special Function
NAC Type - supervised
NAC Type - supervised
NAC Type - supervised
Ignore Open Circuit
NAC Type - supervised
NAC Type - supervised
1
Relay Type - Ignore Open Circuit
2
Relay Type - Ignore Open Circuit
2
NAC Type - supervised
ZONE ASSIGNMENT
Zone Assignment Screen
Adjective/Noun Screen
Programming
63