Appendix D: Wire Requirements - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

T-tapping of the SLC loop wiring is allowed for 2-wire (Class B) configurations. The total resistance of any branch cannot exceed 50 ohms.
The total wire length of all branches cannot exceed 10,000 feet (3,000 m).
Connecting external system accessories to the ES-1000X main circuits must be carefully considered to ensure proper operation. It is import-
ant to use the correct type of wire, gauge and run length for each ES-1000X circuit. Reference the chart below to specify wire requirements
and limitations for each ES-1000X circuit.
Note:
1.
If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by
exclusively employing electronic sounders instead of more electronically noisy notification appliances such as electromechanical bells
or horns.
2.
The SLC can be programmed to operate in LiteSpeed mode (factory default setting) for a quicker device response time. While shielded
wire is not required in LiteSpeed mode, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical
interference. Use the following table to determine the specific wiring requirements for the SLC when unshielded wire is used:
Refer to Table D.1 on page 141 and Table D.2 on page 142 for wiring requirements.
CIRCUIT CONNECTIONS
Circuit Type
SLC loop
(power-limited)
ANN-BUS
(EIA-485)
(power-limited)
monitor module
(power-limited)
monitor module
(power-limited)
control module
(power-limited)
Remote Sync
Output
1
When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023

Appendix D: Wire Requirements

Wire Type and
Circuit Function
Limitations
Connects to
Twisted, shielded pair
Addressable
50 ohms maximum per
Devices
length of Class A loops.
50 ohms per branch
maximum for Class B loops
CLIP MODE
Connects to
Twisted, unshielded pair
Addressable
50 ohms maximum per
Devices
length of Class A loops.
50 ohms per branch
maximum for Class B loops
LITESPEED
MODE
Untwisted, unshielded pair
Connects to
Twisted pair
annunciator
Maximum loop wire
modules/
resistance is 2 ohms for
power and 40 ohms for
data
Initiating Device
Maximum loop wire
Circuit: Contact
resistance is 1500 ohms
Closure
Initiating Device
No more than a 2.4 volt
Circuit: Two-wire
drop allowed at end of
Modules
circuit. Maximum loop wire
resistance is 25 ohms
Notification
In alarm, no more than a
Appliance Circuit
1.2 volt drop allowed at end
of circuit
Provides strobe
Untwisted, unshielded pair
and normal sync
wire
for remote NAC
power supplies
Table D.1 FACP Wire Specifications
WIRE REQUIREMENTS
Recommended
Max. Distance
Wire Gauge and Compatible Brands
Feet (meters)
12,500 (3,750 m)
12 AWG (3.25 mm
Signal 98230, Belden 9583, WPW999
10,000 (3,000 m)
14 AWG (2.00 mm
Signal 98430, Belden 9581, WPW995
6,090 (1,810 m)
16 AWG (1.30 mm
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
4,030 (1,225 m)
18 AWG (0.75 mm
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S
12,500 (3,750 m)
12 AWG (3.25 mm
6020UL, Genesis WG-4315 & WG-4515
10,000 (3,000 m)
14 AWG (2.00 mm
6120UL, Genesis WG-4313 & WG-4513
6,090 (1,810 m)
16 AWG (1.30 mm
6220UL, Genesis WG-4311 & WG-4511
4,030 (1,225 m)
18 AWG (0.75 mm
6320UL, Genesis WG-4306 & WG-4506
1
3,000 (900 m)
12-18 AWG (3.25 - 0.75 mm
6,000 (1,800 m)
Refer to "ANN-BUS Wiring" on page 30 for
information on device wiring
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
Distance limitation
12-18 AWG (3.25 - 0.75 mm
set by 1.2 volt
maximum line drop
Distance set by
12-18 AWG (3.25 - 0.75 mm
295 ohm
resistance
limitation
2
): Genesis 4410,
2
):Genesis 4408 & 4608
2
): Genesis 4406 & 4606
2
): Genesis 4402 & 4602
2
): Belden 5020UL &
2
):Belden 5120UL &
2
): Belden 5220UL &
2
): Belden 5320UL &
2
) using listed wire
2
)
2
)
2
)
2
)