Connecting external system accessories to the main circuits must be carefully considered to ensure proper operation. It is important to
use the correct type of wire, gauge and run length for each circuit. Reference the chart below to specify wire requirements and limitations
for each circuit.
CIRCUIT CONNECTIONS
Circuit Type
Initiating Device Circuit
(power-limited)
ANN-BUS (EIA-485)
power-limited
ANN-BUS Power
24 VDC Regulated,
resettable, nonresettable
Auxiliary Trouble Input
Remote Sync Output
NAC Outputs
D.1 GF-505 NAC Wiring
The following table lists NAC wiring requirements for the GF-505 FACP which utilizes the FLPS-3 power supply.
NAC Load
(Amps)
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2005 Edition)
Table 8, Conductor Properties.
NOTE: These distances reflect the worst case scenario and are based on the current draw of the highest candela strobes at the low end
of the supported NAC voltage with the entire load at the end of the circuit. Further distances can be achieved by performing a point to point
voltage calculation that more accurately reflects the specific devices used and how they are dispersed on the circuit.
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018

Appendix D: Wire Requirements

Circuit Function
Connects to Initiating
Devices
Communication for
ANN-BUS annunciator
and relay modules
Power for ANN-BUS
annunciators
Power for accessories
and 4-wire devices
Open Collector trouble
input for CHG-75,
CHG-120, etc.
Provides strobe and
normal sync for
remote NAC power
supplies
Connects to NAC
devices or Release
devices
Table D.1 FACP Wire Specifications
Max.
allowable
Max. allowable wire pair length
total loop
resistance
AWG 12
AWG 14
(ohms)
solid
solid
6.00
1554
977
3.00
777
489
2.00
518
326
1.50
389
244
1.20
311
195
1.00
259
163
0.86
222
140
0.75
194
122
0.67
173
109
0.60
155
98
Table D.2 NAC Wiring Requirements for FACP with FLPS-3 Power Supply
WIRE REQUIREMENTS
Wire Type and
Limitations
Untwisted, unshielded wire
Distance limitation
(maximum loop resistance
set by 100 ohm
not to exceed 100 ohms)
resistance limitation
Twisted pair a maximum
6,000 (1,800 m)
loop resistance of 120
ohms
Refer to Table 2.2, "Wiring Distances," on page 33 for information on device wiring
Untwisted, unshielded wire
Distance limitation
set by 4 volt
maximum line drop
Single conductor
Distance limitation
20 feet in same
room
Untwisted, unshielded pair
Distance set by 295
wire
ohm resistance
limitation
Untwisted, unshielded pair
Refer to Section D.1 and Section D.2 on page 116.
wire
CLASS-B
(feet)
AWG 16
AWG 18
solid
solid
613
386
307
193
204
129
153
97
123
77
102
64
88
55
77
48
68
43
61
39
Recommended
Max. Distance
Feet (meters)
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
18 AWG (0.75 mm
12-18 AWG (3.25 - 0.75 mm
CLASS-A
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
777
489
307
389
244
153
259
163
102
194
122
77
155
98
61
130
81
51
111
70
44
97
61
38
86
54
34
78
49
31
Wire Gauge
2
)
2
)
2
)
2
)
2
)
AWG 18
solid
193
97
64
48
39
32
28
24
21
19
115